See where PID is enough, and where it isn’t.

Put a controller on a realistic process and run the same tests every time. Each loop is shown the way a mechanical engineer, a control engineer and an automation engineer would look at it, down to the SCL.

Steam pressure drop — One PI vs Cascade
Simulating real-time loop response…

Test Bench

15 controllers on 15 realistic physical plants, or on a model identified from your own data. Auto-tune, inject disturbances, scrub P&ID schematics, and compare scorecards.

Launch Bench

Block Studio

Visually wire transfer functions, PIDs, lead-lag compensators, dead times, nonlinear valves, and scopes on an interactive block canvas.

Launch Block Studio

Worked Case Studies

18 step-by-step industrial problems with live simulations and honest engineering verdicts.

Explore Cases

Process & Controller Encyclopedia

Deep mechanical, control, and PLC/SCL implementation guides for every plant and every rung of the ladder.

Process Plants Showcase

Explore plant dynamics, dead time, and nominal metrics across the catalog.

Liquid flow loop

Flow (m³/h)

Water from a pressure header through a control valve and a magnetic flowmeter. Fast, noisy and self-regulating: the classic loop where a well-tuned PI is all you need.

θ0.3 s
τ1.8 s
K1.6
PID is the answerLag-dominant · θ/τ 0.17

Stirred tank temperature

Temperature (°C)

A jacketed vessel with an agitator, heated through its jacket. Slow, lag-dominant and almost free of dead time: the textbook loop where a well-tuned PID, derivative included, is the answer.

θ36 s
τ850 s
K0.86
PID is the answerLag-dominant · θ/τ 0.04

A buffer vessel between two plant sections. Its job is to keep the outflow smooth by using its own volume. Tight level control is the wrong answer here; a loosely tuned P or PI is the right one.

θ4.5 s
τRamp
K−0.00139
PID is the answerIntegrating

A 2 kg steel mass hanging under an electromagnet with nothing touching it: one axis of a magnetic bearing. It is unstable without control, so the loop can't be slow, and the magnet's pull changes with the gap, so the gain moves with the setpoint.

θ0.0025 s
τ0.029 s
K1
PID is the answerLag-dominant · θ/τ 0.09

A point-down conical tank. The cross-section grows several times from bottom to top, so the process gain and speed change across the range: one PI tuning cannot be right everywhere.

θ3.8 s
τ1200 s
K2
PID falls shortLag-dominant · θ/τ 0.00

A reactor that needs steam when the reaction is quiet and cooling water when it runs hot, from one controller and two valves. Where the output crosses from one valve to the other, the process gain changes threefold.

θ22 s
τ4100 s
K29
PID falls shortLag-dominant · θ/τ 0.01

Steam heat exchanger

Outlet temperature (°C)

Steam heats a process stream through a shell-and-tube exchanger. Steam pressure swings reach the outlet before a temperature loop sees them, and the process flow and inlet temperature are measured: the classic home of cascade and feedforward.

θ9.1 s
τ29 s
K0.67
PID falls shortBalanced · θ/τ 0.31

In-line blending (ratio)

Concentration (%)

A concentrate dosed into a diluent stream that the plant upstream sets. Production changes the diluent flow all the time; the concentration should not care. The textbook case for ratio control.

θ24 s
τ39 s
K1
PID falls shortBalanced · θ/τ 0.63

A screw feeder drops material onto a conveyor, and a weigh belt measures the rate 30 s later. The dead time dwarfs everything else: plain feedback can only be slow, unless the controller predicts what the scale is about to see.

θ33 s
τ5.5 s
K0.8
PID falls shortDead-time dominant · θ/τ 5.95

Boiler drum level

Drum level (mm)

The water level in a boiler drum. More steam demand makes the level rise before it falls (swell); more feedwater makes it dip before it rises (shrink). A level-only controller reacts the wrong way first: this is why boilers use three-element control.

θ46 s
τRamp
K0.00772
PID falls shortIntegrating

Compressor near surge

Discharge pressure (bar)

A fixed-speed gas compressor whose recycle valve holds the discharge pressure. When a user trips, the pressure climbs in seconds and the machine walks up its curve to the surge line: a hard limit the loop must never cross, guarded by a fast override.

θ0.98 s
τ2.4 s
K−0.61
PID falls shortBalanced · θ/τ 0.40

Exothermic batch reactor

Reactor temperature (°C)

A batch reaction that gives off heat, faster the hotter it gets. At the start of the batch that positive feedback eats most of the jacket’s cooling margin: the reactor is four times slower and more sensitive than at the end, and a stronger batch can outrun the jacket altogether. One fixed tuning sees different plants.

θ100 s
τ740 s
K3.9
PID falls shortLag-dominant · θ/τ 0.14

Hot and cold water into one tank. More of either raises the level, and each pulls the temperature its own way: neither valve controls just one thing. Which valve should control what, and does it pay to decouple them or hand both to an MPC?

θ79 s
τ360 s
K0.35
PID falls shortBalanced · θ/τ 0.22

An overhead crane trolley moving a load hanging on an 8 m rope. Every acceleration sets the load swinging with a 5.7 s period and almost no damping. Getting the load to where it should be, without sway, is a job for state feedback.

θ2.3 s
τRamp
K0.05
PID falls shortIntegrating

A motor turning a heavy roll through a long shaft that twists. The shaft and the two inertias ring at 12 Hz with almost no damping, and any speed loop fast enough to matter excites it. The classic place for state feedback (or a notch filter).

θ0.026 s
τ8 s
K10
PID falls shortLag-dominant · θ/τ 0.00

Your plant (identified)

Process value (%)

A model identified from a trend: first or second order plus dead time, or an integrator. No physics, just the input–output behaviour of a real loop, to try strategies on before commissioning.

θ5.4 s
τ20 s
K1
Balanced · θ/τ 0.27

The Controller Ladder

From on-off to model predictive control: climb only as far as your plant demands.

All 15 controllers →

Good places to start

All 18 case studies →