Compressor near surge
A fixed-speed gas compressor whose recycle valve holds the discharge pressure. When a user trips, the pressure climbs in seconds and the machine walks up its curve to the surge line: a hard limit the loop must never cross, guarded by a fast override.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeDead time θ0.975 snothing happens for this long after the valve moves
Time constant τ2.41 sthen 63 % of the way in this long
Gain K−0.607% of span the PV moves per % of valve
Balanced (0.2 ≤ θ/τ < 1) — ModerateDelay share: 28.8% (θ/τ = 0.4)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 6 bar:
Verdict: PID falls short
An anti-surge override on the surge approach, plus feedforward from the users' flow, on top of an ordinary pressure PI.
- A pressure PI alone walks the machine into surge both on a trip and when its setpoint is pushed past the curve.
- The override holds a setpoint past the curve short of the surge line, but reacts too late to a trip on the flat top of the curve.
- Feedforward catches the trip (the approach peaks well short of the line) but does nothing for a setpoint that is simply too high.
- Together they keep the machine out of surge in every test. That is the shape of real anti-surge systems: a control line, a fast controller, and something that acts before the flow falls.
On Compare controllers, feedforward has the smallest errors overall, but it crosses the surge line when the setpoint is pushed too high. Only the override keeps to the line in every test. Here the line matters more than the error.