PID

Proportional, integral and derivative action on the error. Something like nine out of ten industrial loops are PI, and most of the rest are PID. The lab's baseline, and very often the verdict.

Theory

The ideal (ISA, non-interacting) form with setpoint weights, as PID_Compact implements it:

u=Kc[(b r−y)+1Ti∫(r−y) dt+Td ddt(c r−y1+aTds)]u = K_c\Big[(b\,r - y) + \frac{1}{T_i}\int (r - y)\,dt + T_d\,\frac{d}{dt}\Big(\frac{c\,r - y}{1 + a T_d s}\Big)\Big]
  • P reacts to the error now. On its own it leaves an offset on a self-regulating process.
  • I removes the offset by integrating until the error is zero. It adds phase lag below ω=1/Ti\omega = 1/T_i.
  • D reacts to the error's rate of change and adds phase lead, which lets you raise the gain on lag-dominant processes. The filter 1/(1+aTds)1/(1 + aT_d s) caps its high-frequency gain at Kc(1+1/a)K_c(1 + 1/a).
  • Setpoint weights bb and cc shape the response to setpoint changes without changing the response to disturbances. With c=0c = 0 there is no derivative kick when the setpoint steps.

Forms you will meet.

  • Parallel: Kp=KcK_p = K_c, Ki=Kc/TiK_i = K_c/T_i, Kd=KcTdK_d = K_c T_d.
  • Series (interacting): Kc′(1+1/Ti′s)(1+Td′s)K_c'(1 + 1/T_i's)(1 + T_d's). Convert to ideal with Kc=Kc′(1+Td′/Ti′)K_c = K_c'(1 + T_d'/T_i'), Ti=Ti′+Td′T_i = T_i' + T_d', Td=Ti′Td′/(Ti′+Td′)T_d = T_i'T_d'/(T_i' + T_d').

In the frequency domain. The loop is shaped so ∣L(jω)∣|L(j\omega)| crosses 1 where the phase still has margin (PM ≥ 45°, GM ≥ 6 dB). Peak sensitivity Ms=max⁡∣1/(1+L)∣M_s = \max |1/(1 + L)| combines both: below 1.4 is robust, above 2 fragile.

When it works, and when it breaks

Works
  • Self-regulating and integrating processes with modest dead time (θ/τ below about 1).

  • Processes whose gain and dynamics stay roughly the same over the operating range.

  • Most flow, pressure, temperature and level loops in a plant.

Breaks
  • Gain or dynamics that change a lot across the range: one tuning cannot fit (→ gain scheduling, characterization).

  • Dead time much longer than the time constant: the gain has to be cut so far that load rejection is slow (→ Smith predictor, IMC).

  • Measured disturbances that hit faster than feedback can react (→ feedforward, cascade).

  • Constraints and coupled variables (→ override, decoupling, MPC).

How to tune it

  1. Bump test in manual. Step the output 5–10 % and read off gain KK, time constant τ\tau and dead time θ\theta. The lab's linearization shows the same model.
  2. Pick a rule for what the loop is for.
    • Lambda/IMC gives a smooth setpoint response with no overshoot.
    • SIMC with τc=θ\tau_c = \theta gives fast, still robust control. Use a larger τc\tau_c to calm it.
    • AMIGO is a robust default for load rejection.
    • Ziegler–Nichols and Cohen–Coon are aggressive. They are good to recognise, but rarely what you want.
  3. Check robustness, not just the step: margins, MsM_s, and the response with the plant changed by ±30 %.
  4. Check the valve. CV activity and travel tell you whether noise is reaching the actuator.
The tuning rules in the lab
SIMC (Skogestad) (PI, PID)
Kc=τK(τc+θ),Ti=min⁡(τ, 4(τc+θ))K_c = \frac{\tau}{K(\tau_c + \theta)},\quad T_i = \min\big(\tau,\ 4(\tau_c + \theta)\big)

Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.

Lambda (IMC) (PI)
Kc=τK(λ+θ),Ti=τK_c = \frac{\tau}{K(\lambda + \theta)},\quad T_i = \tau

The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.

IMC-PID (Rivera–Morari–Skogestad) (PI, PID)
Kc=2τ+θ2Kλ,Ti=τ+θ2PID: Kc=2τ+θK(2λ+θ), Td=τθ2τ+θK_c = \frac{2\tau + \theta}{2K\lambda},\quad T_i = \tau + \frac{\theta}{2}\qquad\text{PID: } K_c = \frac{2\tau + \theta}{K(2\lambda + \theta)},\ T_d = \frac{\tau\theta}{2\tau + \theta}

Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.

Lambda for integrating (averaging level) (P, PI)
Kc=2λ+θk′(λ+θ)2,Ti=2λ+θK_c = \frac{2\lambda + \theta}{k'(\lambda + \theta)^2},\quad T_i = 2\lambda + \theta

For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.

Ziegler–Nichols (reaction curve) (P, PI, PID)
Kc=0.9 τKθ,Ti=3.33 θK_c = \frac{0.9\,\tau}{K\theta},\quad T_i = 3.33\,\theta

The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.

Cohen–Coon (P, PI, PID)
Kc=τKθ(0.9+θ12τ),Ti=θ 30+3θ/τ9+20θ/τK_c = \frac{\tau}{K\theta}\Big(0.9 + \frac{\theta}{12\tau}\Big),\quad T_i = \theta\,\frac{30 + 3\theta/\tau}{9 + 20\theta/\tau}

Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.

AMIGO (Åström–Hägglund) (PI, PID)
Kc=0.15K+(0.35−θτ(θ+τ)2)τKθ,Ti=0.35θ+13θτ2τ2+12θτ+7θ2K_c = \frac{0.15}{K} + \Big(0.35 - \frac{\theta\tau}{(\theta+\tau)^2}\Big)\frac{\tau}{K\theta},\quad T_i = 0.35\theta + \frac{13\theta\tau^2}{\tau^2 + 12\theta\tau + 7\theta^2}

Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.

How to implement it

Discrete form (called every TsT_s):

  • Backward-Euler derivative on the filtered c r−yc\,r - y.
  • Integral kept in output units, I+=KcTse/TiI \mathrel{+}= K_c T_s e / T_i, so changing gains online doesn't bump the output.

Anti-windup.

  • Conditional integration: don't integrate further into a limit.
  • Back-calculation: bleed the integral by (usat−u) Ts/Tt(u_{sat} - u)\,T_s/T_t.

Bumpless manual → auto. In manual, keep setting I=umanual−PI = u_{manual} - P so the first automatic cycle starts from the manual output.

Sample time. At least 10 per dominant time constant, and under a fifth of the dead time if there is real dead time. Call the block from a fixed cyclic interrupt, never from the free-running main cycle.

Siemens and elsewhere

Siemens
  • PID_Compact (continuous output, or PWM) is the standard choice.
  • PID_3Step drives valve actuators with open/close outputs and no positioner.
  • PID_Temp handles heating/cooling split outputs.
  • Call them from OB30–OB38 at a cycle that matches CtrlParams.Cycle.
  • The gain is in engineering units (Gain = Kc × 100 / span when the input is scaled).
  • Pretuning and fine tuning (relay-based) are available in the commissioning editor.
  • The custom LL_PID export reproduces exactly the algorithm in the lab, for when you need back-calculation or online gain changes.
Elsewhere
  • CODESYS: Util PID (KP, TN, TV in seconds).
  • TwinCAT: Tc2_ControllerToolbox FB_CTRL_PID.
  • Rockwell PIDE: independent or dependent gains, with times in minutes.
  • DCS (DeltaV, 800xA, Experion): usually the ISA form with gain, reset and rate, sometimes as reset in repeats per minute.

Always check the form (ideal, series or parallel) and the time units before copying numbers between systems.

Interactive Controller Sandbox

Test and tune PID live on a process, benchmark against baseline PI, and inspect the resulting code.

Interactive Gains (Primary Loop)

Drag sliders or nudge gains to observe the closed-loop transient response
Kc (gain): 0.45
Ti (integral): 1.8 s
Td (derivative): 0 s

Closed-Loop Response: PID vs Baseline PI

Simulating…
Running test scenarios…
Block Diagram
SP rΣ+−PIDKc·(1 + 1/Ti·s + Td·s)PIDCV uValve1/(τᵥs + 1), char.stemΣ++d: header pressureProcessQ = K_v f √ΔpPV yTransmittere^(−θs)/(τₘs + 1)Σ++noise nPV measured
Generated code
// Loop Lab export: Liquid flow loop, FIC-101
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.

FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
   VAR_INPUT
      Setpoint : Real;        // engineering units
      Input : Real;           // measurement, engineering units
      ManualEnable : Bool;    // TRUE = manual: Output follows ManualValue
      ManualValue : Real;     // %
      Feedforward : Real;     // %, added to the output (0 when unused)
      HoldIntegral : Int;     // +1 / -1: don't integrate up / down (a cascade slave is saturated)
      ExtResetEnable : Bool;  // override: this controller is not selected, so its integral follows ExtReset
      ExtReset : Real;        // %, the selected (valve) output, for external reset feedback
      Cycle : Real := 0.1;    // s, must match the cyclic interrupt the block is called from
   END_VAR
   VAR_OUTPUT
      Output : Real;          // %
      AtLimit : Int;          // +1 / -1 when the output is pinned high / low
   END_VAR
   VAR
      Gain : Real := 0.45;        // % output per % of span
      Ti : Real := 1.8;          // s, 0 = no integral action
      Td : Real := 0.0;          // s, 0 = no derivative action
      PWeighting : Real := 1.0;   // setpoint weight b on P
      DWeighting : Real := 0.0;   // setpoint weight c on D
      TdFiltRatio : Real := 0.1;  // derivative filter = TdFiltRatio * Td
      InLow : Real := 0.0;
      InHigh : Real := 60.0;
      OutLow : Real := 0.0;
      OutHigh : Real := 100.0;
      Invert : Bool := FALSE;
      Integral : Real;        // integral term, in % output (so gain changes don't bump)
      DTerm : Real;
      LastED : Real;
   END_VAR
   VAR_TEMP
      sp : Real;
      pv : Real;
      dir : Real;
      e : Real;
      eP : Real;
      eD : Real;
      p : Real;
      tf : Real;
      iNext : Real;
      v : Real;
      u : Real;
   END_VAR

BEGIN
    // Scale to % of span: the gains are then independent of engineering units.
    #sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
    #pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
    #dir := 1.0;
    IF #Invert THEN
        #dir := -1.0;
    END_IF;
    #e := #dir * (#sp - #pv);
    #eP := #dir * (#PWeighting * #sp - #pv);
    #eD := #dir * (#DWeighting * #sp - #pv);
    #p := #Gain * #eP;

    IF #ManualEnable THEN
        // Track: preload the integral so switching to auto doesn't bump the output.
        #u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
        #Integral := #u - #p - #Feedforward;
        #DTerm := 0.0;
        #LastED := #eD;
        #Output := #u;
        #AtLimit := 0;
        RETURN;
    END_IF;

    // Derivative on c*SP - PV through a first-order filter (backward Euler).
    IF #Td > 0.0 THEN
        #tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
        #DTerm := #tf / (#tf + #Cycle) * #DTerm
                  + #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
    ELSE
        #DTerm := 0.0;
    END_IF;
    #LastED := #eD;

    IF #ExtResetEnable AND #Ti > 0.0 THEN
        // External reset feedback: the integral follows the selected output through a Ti lag,
        // so this controller's output is the valve signal plus its own P and D.
        #iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
    ELSIF #Ti > 0.0 THEN
        #iNext := #Integral + #Gain * #Cycle / #Ti * #e;
    ELSE
        #iNext := #Integral;
    END_IF;

    #v := #p + #iNext + #DTerm + #Feedforward;
    #u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);

    // A saturated slave asks its master to stop integrating in that direction.
    IF #ExtResetEnable THEN
        #Integral := #iNext;
    ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
        // Conditional integration: stop integrating while the output is pinned and the error pushes it further.
        IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
            #Integral := #iNext;
        END_IF;
    END_IF;

    IF #v > #OutHigh THEN
        #AtLimit := 1;
    ELSIF #v < #OutLow THEN
        #AtLimit := -1;
    ELSE
        #AtLimit := 0;
    END_IF;
    #Output := #u;
END_FUNCTION_BLOCK

// OB30 "Cyclic interrupt", cycle time 0.1 s (100 ms).
// "FT-101" is the scaled input (NORM_X/SCALE_X from the analog card), "FV-101" the output to scale back to 0-27648.
"FIC_101_DB"(Setpoint := "SP", Input := "FT-101", ManualEnable := "Manual", ManualValue := "ManualOut");
"FV-101" := "FIC_101_DB".Output;