Processes

Each plant is a realistic physical system with distinct dynamics, non-linearities, and sensor noise. Inspect the mechanical and control blueprints, or experiment with controllers on the live bench.

Where PID is the answer

4 plants

Liquid flow loop

Flow (m³/h)

Water from a pressure header through a control valve and a magnetic flowmeter. Fast, noisy and self-regulating: the classic loop where a well-tuned PI is all you need.

Dead time θ0.3 s
Time const τ1.8 s
Gain K1.6
PID is the answerLag-dominant · θ/τ 0.17

Stirred tank temperature

Temperature (°C)

A jacketed vessel with an agitator, heated through its jacket. Slow, lag-dominant and almost free of dead time: the textbook loop where a well-tuned PID, derivative included, is the answer.

Dead time θ36 s
Time const τ850 s
Gain K0.86
PID is the answerLag-dominant · θ/τ 0.04

A buffer vessel between two plant sections. Its job is to keep the outflow smooth by using its own volume. Tight level control is the wrong answer here; a loosely tuned P or PI is the right one.

Dead time θ4.5 s
Time const τIntegrating
Gain K-0.00139 /s
PID is the answerIntegrating

A 2 kg steel mass hanging under an electromagnet with nothing touching it: one axis of a magnetic bearing. It is unstable without control, so the loop can't be slow, and the magnet's pull changes with the gap, so the gain moves with the setpoint.

Dead time θ0.0025 s
Time const τ0.029 s
Gain K1
PID is the answerLag-dominant · θ/τ 0.09

Where PID falls short

11 plants

A point-down conical tank. The cross-section grows several times from bottom to top, so the process gain and speed change across the range: one PI tuning cannot be right everywhere.

Dead time θ3.8 s
Time const τ1200 s
Gain K2
PID falls shortLag-dominant · θ/τ 0.00

A reactor that needs steam when the reaction is quiet and cooling water when it runs hot, from one controller and two valves. Where the output crosses from one valve to the other, the process gain changes threefold.

Dead time θ22 s
Time const τ4100 s
Gain K29
PID falls shortLag-dominant · θ/τ 0.01

Steam heat exchanger

Outlet temperature (°C)

Steam heats a process stream through a shell-and-tube exchanger. Steam pressure swings reach the outlet before a temperature loop sees them, and the process flow and inlet temperature are measured: the classic home of cascade and feedforward.

Dead time θ9.1 s
Time const τ29 s
Gain K0.67
PID falls shortBalanced · θ/τ 0.31

In-line blending (ratio)

Concentration (%)

A concentrate dosed into a diluent stream that the plant upstream sets. Production changes the diluent flow all the time; the concentration should not care. The textbook case for ratio control.

Dead time θ24 s
Time const τ39 s
Gain K1
PID falls shortBalanced · θ/τ 0.63

A screw feeder drops material onto a conveyor, and a weigh belt measures the rate 30 s later. The dead time dwarfs everything else: plain feedback can only be slow, unless the controller predicts what the scale is about to see.

Dead time θ33 s
Time const τ5.5 s
Gain K0.8
PID falls shortDead-time dominant · θ/τ 5.95

Boiler drum level

Drum level (mm)

The water level in a boiler drum. More steam demand makes the level rise before it falls (swell); more feedwater makes it dip before it rises (shrink). A level-only controller reacts the wrong way first: this is why boilers use three-element control.

Dead time θ46 s
Time const τIntegrating
Gain K0.00772 /s
PID falls shortIntegrating

Compressor near surge

Discharge pressure (bar)

A fixed-speed gas compressor whose recycle valve holds the discharge pressure. When a user trips, the pressure climbs in seconds and the machine walks up its curve to the surge line: a hard limit the loop must never cross, guarded by a fast override.

Dead time θ0.98 s
Time const τ2.4 s
Gain K-0.61
PID falls shortBalanced · θ/τ 0.40

Exothermic batch reactor

Reactor temperature (°C)

A batch reaction that gives off heat, faster the hotter it gets. At the start of the batch that positive feedback eats most of the jacket’s cooling margin: the reactor is four times slower and more sensitive than at the end, and a stronger batch can outrun the jacket altogether. One fixed tuning sees different plants.

Dead time θ100 s
Time const τ740 s
Gain K3.9
PID falls shortLag-dominant · θ/τ 0.14

Hot and cold water into one tank. More of either raises the level, and each pulls the temperature its own way: neither valve controls just one thing. Which valve should control what, and does it pay to decouple them or hand both to an MPC?

Dead time θ79 s
Time const τ360 s
Gain K0.35
PID falls shortBalanced · θ/τ 0.22

An overhead crane trolley moving a load hanging on an 8 m rope. Every acceleration sets the load swinging with a 5.7 s period and almost no damping. Getting the load to where it should be, without sway, is a job for state feedback.

Dead time θ2.3 s
Time const τIntegrating
Gain K0.05 /s
PID falls shortIntegrating

A motor turning a heavy roll through a long shaft that twists. The shaft and the two inertias ring at 12 Hz with almost no damping, and any speed loop fast enough to matter excites it. The classic place for state feedback (or a notch filter).

Dead time θ0.026 s
Time const τ8 s
Gain K10
PID falls shortLag-dominant · θ/τ 0.00

Your own data

1 plant

Your plant (identified)

Process value (%)

A model identified from a trend: first or second order plus dead time, or an integrator. No physics, just the input–output behaviour of a real loop, to try strategies on before commissioning.

Dead time θ5.4 s
Time const τ20 s
Gain K1
Balanced · θ/τ 0.27