Reactor temperature (split-range)
A reactor that needs steam when the reaction is quiet and cooling water when it runs hot, from one controller and two valves. Where the output crosses from one valve to the other, the process gain changes threefold.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeDead time θ21.9 snothing happens for this long after the valve moves
Time constant τ4080 sthen 63 % of the way in this long
Gain K29.1% of span the PV moves per % of valve
Lag-dominant (θ/τ < 0.2) — Easy for PIDelay share: 0.5% (θ/τ = 0.0054)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 60 °C:
Verdict: PID falls short
Balance the split, then tune one loop.
- Split at 50 %, a PI tuned on steam hunts between the valves once the reaction needs cooling (linearly unstable there). One tuned on cooling overshoots setpoint changes by about 23 %.
- Move the split to about 76 % (or characterize the output) and one tuning gives 5–8 % overshoot on both sides, with the same margin everywhere.
- Keep the gap small: 6 % of gap made the temperature wander four times more near the split.
- With the split balanced, derivative halves the load swings again, for about seven times the valve travel. Nothing further up the ladder beats that overall.
The fix is a valve setting, not a smarter controller.