Gain-scheduled PID
A PID whose gains are looked up from where the process is. You linearize at a few operating points, tune each one, and interpolate between them. The standard fix when a process's gain changes across its range.
Theory
If the plant near operating point behaves like , tune a controller for each one, then let the gains follow a scheduling variable that tracks the operating point:
The "frozen" assumption. Each local design assumes the gains stay put long enough for the loop to behave like its linear model. That requires the scheduling variable to change slowly compared with the closed-loop dynamics.
Choosing the variable.
- Schedule on PV when the nonlinearity lives in the process state (level in a cone).
- Schedule on SP when you want the gains to move ahead of the process on setpoint changes.
- Schedule on an external measurement (throughput, production rate) when that is what moves the dynamics.
Scheduling on PV closes an extra loop through the gains: fast PV swings make the gains swing too.
When it works, and when it breaks
Gain or time constants that change smoothly and predictably with a measurable variable.
Plants you can bump-test at several operating points but have no formula for.
A known operating schedule (throughput levels, product grades).
Scheduling variables that move as fast as the loop itself: the frozen assumption fails.
Too few breakpoints over a strong nonlinearity: the interpolation is wrong in between.
Gain changes that bump the output (the integral is not kept in output units).
Maintenance: every breakpoint is a set of numbers someone has to understand and retune.
How to tune it
- Choose 3–5 operating points across the range, more where the gain changes fastest.
- Bump test (or linearize) at each one and tune with the same rule and the same closed-loop speed, so the loop behaves the same everywhere.
- Check the margins between breakpoints too, not just at them.
- Run setpoint steps that cross breakpoints, and confirm there is no bump when the gains change.
The tuning rules in the lab
Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.
The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.
Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.
For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.
The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.
Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.
Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.
How to implement it
- Interpolate linearly, and hold the end values flat outside the table.
- Keep the PID's integral in output units so a gain change doesn't move the output.
- Optionally rate-limit the scheduled gains.
- Log the active gains with the trend: it's the first thing you need when someone asks why the loop did something.
Siemens and elsewhere
- Lookup: an FC interpolating over breakpoints (exported as LL_Schedule) writes Gain, Ti and Td into the PID instance every cycle.
- With PID_Compact: write Retain.CtrlParams, and test bumplessness on your firmware.
- With the custom LL_PID: the integral is already in output units, so gain changes don't bump.
- Sharing: store the breakpoints in a DB so they can be edited from the HMI by authorised users.
Many DCS PID blocks have built-in gain scheduling, or "adaptive gain" tables keyed on an external variable. Flight control systems are the textbook case: schedules on dynamic pressure and Mach number.
Interactive Controller Sandbox
Test and tune Gain-scheduled PID live on a process, benchmark against baseline PI, and inspect the resulting code.
Interactive Gains (Primary Loop)
Drag sliders or nudge gains to observe the closed-loop transient responseClosed-Loop Response: Gain scheduling vs Baseline PI
Simulating…// Loop Lab export: Conical tank level, LIC-201
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.
FUNCTION "LL_Schedule" : Void
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
X : Real; // scheduling variable
END_VAR
VAR_OUTPUT
Gain : Real;
Ti : Real;
Td : Real;
END_VAR
VAR_TEMP
w : Real;
END_VAR
BEGIN
// Linear interpolation between the breakpoints, held flat outside them.
IF #X <= 0.4 THEN
#Gain := 3.0;
#Ti := 245.0;
#Td := 0.0;
ELSIF #X <= 1.0 THEN
#w := (#X - 0.4) / 0.6;
#Gain := 3.0 + #w * (3.0 - 3.0);
#Ti := 245.0 + #w * (245.0 - 245.0);
#Td := 0.0 + #w * (0.0 - 0.0);
ELSIF #X <= 1.6 THEN
#w := (#X - 1.0) / 0.6;
#Gain := 3.0 + #w * (3.0 - 3.0);
#Ti := 245.0 + #w * (245.0 - 245.0);
#Td := 0.0 + #w * (0.0 - 0.0);
ELSE
#Gain := 3.0;
#Ti := 245.0;
#Td := 0.0;
END_IF;
END_FUNCTION
FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
Setpoint : Real; // engineering units
Input : Real; // measurement, engineering units
ManualEnable : Bool; // TRUE = manual: Output follows ManualValue
ManualValue : Real; // %
Feedforward : Real; // %, added to the output (0 when unused)
HoldIntegral : Int; // +1 / -1: don't integrate up / down (a cascade slave is saturated)
ExtResetEnable : Bool; // override: this controller is not selected, so its integral follows ExtReset
ExtReset : Real; // %, the selected (valve) output, for external reset feedback
Cycle : Real := 0.5; // s, must match the cyclic interrupt the block is called from
END_VAR
VAR_OUTPUT
Output : Real; // %
AtLimit : Int; // +1 / -1 when the output is pinned high / low
END_VAR
VAR
Gain : Real := 3.0; // % output per % of span
Ti : Real := 245.0; // s, 0 = no integral action
Td : Real := 0.0; // s, 0 = no derivative action
PWeighting : Real := 1.0; // setpoint weight b on P
DWeighting : Real := 0.0; // setpoint weight c on D
TdFiltRatio : Real := 0.1; // derivative filter = TdFiltRatio * Td
InLow : Real := 0.0;
InHigh : Real := 2.0;
OutLow : Real := 0.0;
OutHigh : Real := 100.0;
Invert : Bool := FALSE;
Integral : Real; // integral term, in % output (so gain changes don't bump)
DTerm : Real;
LastED : Real;
END_VAR
VAR_TEMP
sp : Real;
pv : Real;
dir : Real;
e : Real;
eP : Real;
eD : Real;
p : Real;
tf : Real;
iNext : Real;
v : Real;
u : Real;
END_VAR
BEGIN
// Scale to % of span: the gains are then independent of engineering units.
#sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
#pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
#dir := 1.0;
IF #Invert THEN
#dir := -1.0;
END_IF;
#e := #dir * (#sp - #pv);
#eP := #dir * (#PWeighting * #sp - #pv);
#eD := #dir * (#DWeighting * #sp - #pv);
#p := #Gain * #eP;
IF #ManualEnable THEN
// Track: preload the integral so switching to auto doesn't bump the output.
#u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
#Integral := #u - #p - #Feedforward;
#DTerm := 0.0;
#LastED := #eD;
#Output := #u;
#AtLimit := 0;
RETURN;
END_IF;
// Derivative on c*SP - PV through a first-order filter (backward Euler).
IF #Td > 0.0 THEN
#tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
#DTerm := #tf / (#tf + #Cycle) * #DTerm
+ #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
ELSE
#DTerm := 0.0;
END_IF;
#LastED := #eD;
IF #ExtResetEnable AND #Ti > 0.0 THEN
// External reset feedback: the integral follows the selected output through a Ti lag,
// so this controller's output is the valve signal plus its own P and D.
#iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
ELSIF #Ti > 0.0 THEN
#iNext := #Integral + #Gain * #Cycle / #Ti * #e;
ELSE
#iNext := #Integral;
END_IF;
#v := #p + #iNext + #DTerm + #Feedforward;
#u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);
// A saturated slave asks its master to stop integrating in that direction.
IF #ExtResetEnable THEN
#Integral := #iNext;
ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
// Conditional integration: stop integrating while the output is pinned and the error pushes it further.
IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
#Integral := #iNext;
END_IF;
END_IF;
IF #v > #OutHigh THEN
#AtLimit := 1;
ELSIF #v < #OutLow THEN
#AtLimit := -1;
ELSE
#AtLimit := 0;
END_IF;
#Output := #u;
END_FUNCTION_BLOCK
// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "LT-201" is the scaled input (NORM_X/SCALE_X from the analog card), "LV-201" the output to scale back to 0-27648.
// Look up the gains for where the process is now, then run the PID with them.
"LL_Schedule"(X := "LT-201", Gain => "LIC_201_DB".Gain, Ti => "LIC_201_DB".Ti, Td => "LIC_201_DB".Td);
"LIC_201_DB"(Setpoint := "SP", Input := "LT-201", ManualEnable := "Manual", ManualValue := "ManualOut");
"LV-201" := "LIC_201_DB".Output;