Boiler drum level

The water level in a boiler drum. More steam demand makes the level rise before it falls (swell); more feedwater makes it dip before it rises (shrink). A level-only controller reacts the wrong way first: this is why boilers use three-element control.

Plant Dynamics at Nominal Point

FOPDT dynamics & controllability regime
Open on the bench🧩 Build in Block Studio
Dead time θ46.5 snothing happens for this long after the valve moves
Time constant τ—no settling: it ramps
Ramp rate k′0.00772 /s% of span per second, per % of valve
Integrating (1/s) — Needs careful reset TiIntegrating process (no self-regulation)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 0 mm:
G(s)≈0.00772 e−46.5ssG(s) \approx \frac{0.00772\,e^{-46.5s}}{s}
Verdict: PID falls short

Three-element control.

  • A level-only PI either has to be slow (about 100–160 mm swings on load steps, nowhere near recovered in five minutes) or is fragile, and a 50 % swell increase takes it to the valve limits.
  • Steam-flow feedforward cuts the load-step swings to about 20–35 mm.
  • The feedwater flow loop removes pump-pressure upsets almost entirely.
  • Together, the total IAE falls by three quarters.

This is the textbook case of the controller ladder done right: each element fixes one specific, physical problem.