On-off with hysteresis

A relay: full output below the setpoint, none above, with a hysteresis band so it doesn't chatter. The simplest controller there is, and still the right one for thermostats, sump pumps and many heaters.

Theory

u={uone>b/2uoffe<−b/2unchangedotherwiseu = \begin{cases} u_{on} & e > b/2 \\ u_{off} & e < -b/2 \\ \text{unchanged} & \text{otherwise} \end{cases}

An on-off loop never settles: it limit-cycles. Each time the output switches, the process carries on moving for about one dead time before it notices. The swing is therefore roughly the hysteresis band plus what the process covers in that time: ±(b/2+K Δu θ/τ)\pm\big(b/2 + K\,\Delta u\,\theta/\tau\big).

The describing function of a relay, N(a)=4M/(πa)N(a) = 4M/(\pi a), predicts where the cycle settles: where G(jω)=−1/N(a)G(j\omega) = -1/N(a).

When it works, and when it breaks

Works
  • Slow processes with a lot of capacity, where a few percent of swing doesn't matter (room heating, tank top-up, sump pumps).

  • Actuators that only have two states: contactors, solenoid valves, single-speed pumps.

Breaks
  • Anything that needs to hold a value closely: it always cycles.

  • Modulating valves and drives: switching between 0 and 100 % wears them out fast.

  • Processes with dead time: the swing grows with θ/τ.

How to tune it

There is only the hysteresis band, and it trades swing against switching rate. Widen it until the actuator's starts per hour are acceptable (motors and contactors have a rated number). For heaters, time-proportioning (PWM) turns the same relay into a proportional controller.

How to implement it

Compare against SP ± b/2 and keep the state: inside the band the output does not change. Add minimum on and off times for motors and compressors. Make the band large enough to cover the measurement noise, or noise alone will toggle the output.

Siemens and elsewhere

Siemens

A few lines of SCL or LAD with a set/reset (SR) bistable. For heaters on an S7-1200/1500, PID_Compact's Output_PWM or CTRL_PWM gives time-proportioning from a PID output instead.

Elsewhere

Every platform has a hysteresis/comparator block (CODESYS Util HYSTERESIS, for example). Building management systems run on-off with dead bands almost everywhere.

Interactive Controller Sandbox

Test and tune On-off with hysteresis live on a process, benchmark against baseline PI, and inspect the resulting code.

Closed-Loop Response: On-off vs Baseline PI

Simulating…
Running test scenarios…
Block Diagram
SP rΣ+−Relay± 2 % bandCV uValve1/(τᵥs + 1), char.stemΣ++d: header pressureProcessQ = K_v f √ΔpPV yTransmittere^(−θs)/(τₘs + 1)Σ++noise nPV measured
Generated code
// Loop Lab export: Liquid flow loop, FIC-101
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.

FUNCTION_BLOCK "LL_OnOff"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
   VAR_INPUT
      Setpoint : Real;    // m³/h
      Input : Real;       // m³/h
   END_VAR
   VAR_OUTPUT
      Output : Real;      // %
   END_VAR
   VAR
      Hysteresis : Real := 1.2;   // m³/h, total band
      OutOn : Real := 100.0;
      OutOff : Real := 0.0;
      IsOn : Bool;
   END_VAR

BEGIN
    IF #Input < #Setpoint - #Hysteresis / 2.0 THEN
        #IsOn := TRUE;
    ELSIF #Input > #Setpoint + #Hysteresis / 2.0 THEN
        #IsOn := FALSE;
    END_IF;
    IF #IsOn THEN
        #Output := #OutOn;
    ELSE
        #Output := #OutOff;
    END_IF;
END_FUNCTION_BLOCK

// OB30 "Cyclic interrupt", cycle time 0.1 s (100 ms).
// "FT-101" is the scaled input (NORM_X/SCALE_X from the analog card), "FV-101" the output to scale back to 0-27648.
"FIC_101_DB"(Setpoint := "SP", Input := "FT-101");
"FV-101" := "FIC_101_DB".Output;