Stirred tank temperature
A jacketed vessel with an agitator, heated through its jacket. Slow, lag-dominant and almost free of dead time: the textbook loop where a well-tuned PID, derivative included, is the answer.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeDead time θ35.9 snothing happens for this long after the valve moves
Time constant τ846 sthen 63 % of the way in this long
Gain K0.861% of span the PV moves per % of valve
Lag-dominant (θ/τ < 0.2) — Easy for PIDelay share: 4.1% (θ/τ = 0.042)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 60 °C:
Verdict: PID is the answer
PID, derivative included, with its filter set sensibly. Derivative cuts the worst upset by about a third and makes the loop more robust at the same time, because its phase lead pays for the extra gain. The cost is valve activity: about 4× a PI's with a filter ratio of 0.5, about 12× with 0.1. If the actuator can't take that, a SIMC-tuned PI is an honest second. Nothing further up the ladder is needed.