Ratio control

The controlled flow follows a wild flow that something else sets, at a set ratio: SP = R × wild flow. An analyzer or quality controller may trim the ratio. The product stays right through every production change, and the trim's loop gain stops depending on the rate.

Theory

Many processes care about a proportion: fuel to air, reagent to feed, concentrate to diluent. If the proportion is right, the product is right, whatever the throughput. Ratio control holds the proportion directly:

FB,sp=R×FAF_{B,sp} = R \times F_A
  • FAF_A is the wild flow, measured but set elsewhere (production rate).
  • FBF_B is the controlled flow, with its own flow loop.

Fixed ratio is pure feedforward: no quality measurement at all. It is right only as long as the recipe ratio is right.

Trimmed ratio adds a slow outer controller on the product quality that adjusts RR. That is cascade, with a multiplication in the middle. Linearized at one throughput,

δFB,sp=R0 δFA+FA0 δR\delta F_{B,sp} = R_0\,\delta F_A + F_{A0}\,\delta R

that is, feedforward gain R0R_0 from the wild flow, plus the trim's output scaled by FA0F_{A0}.

Why not just additive feedforward? The quality usually depends on the ratio, not on the flow. With ratio control the trim's loop gain, ∂c/∂R\partial c/\partial R, doesn't depend on the throughput. With additive feedforward it does (here 3 : 1 between low and high rate), so one tuning is too fast at low rate and too slow at high rate.

When it works, and when it breaks

Works
  • Blending, dosing and dilution: chemicals into water, additives into fuel, concentrate into product.

  • Combustion: air follows fuel (often with cross-limiting so air leads on increases and lags on decreases).

  • Any process where the quality depends on a proportion and the throughput is set elsewhere.

Breaks
  • The two meters disagree (different bases, drift): the ratio is wrong without anyone seeing it.

  • Very low wild flow: the ratio of a noisy, near-zero signal is noise. Cut off below a minimum.

  • Different dynamics on the two streams: one arrives before the other, and the product shows a transient on every rate change (add a lead-lag on the wild flow).

  • Unmeasured changes in either stream's composition: only a trim on a quality measurement catches them.

How to tune it

  1. The flow loop first, fast and well damped, on its own setpoint.
  2. The ratio from the recipe: the mass balance, R=FB/FAR = F_B/F_A at the design point.
  3. The trim on the quality measurement, with the flow loop and the ratio closed. Its process is "ratio → quality": tune it on a step in RR. It includes the analyzer delay, so it is slow.
  4. Limit the ratio range the trim may use, so a failed analyzer can't drive it anywhere absurd.
The tuning rules in the lab
SIMC (Skogestad) (PI, PID)
Kc=τK(τc+θ),Ti=min⁡(τ, 4(τc+θ))K_c = \frac{\tau}{K(\tau_c + \theta)},\quad T_i = \min\big(\tau,\ 4(\tau_c + \theta)\big)

Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.

Lambda (IMC) (PI)
Kc=τK(λ+θ),Ti=τK_c = \frac{\tau}{K(\lambda + \theta)},\quad T_i = \tau

The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.

IMC-PID (Rivera–Morari–Skogestad) (PI, PID)
Kc=2τ+θ2Kλ,Ti=τ+θ2PID: Kc=2τ+θK(2λ+θ), Td=τθ2τ+θK_c = \frac{2\tau + \theta}{2K\lambda},\quad T_i = \tau + \frac{\theta}{2}\qquad\text{PID: } K_c = \frac{2\tau + \theta}{K(2\lambda + \theta)},\ T_d = \frac{\tau\theta}{2\tau + \theta}

Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.

Lambda for integrating (averaging level) (P, PI)
Kc=2λ+θk′(λ+θ)2,Ti=2λ+θK_c = \frac{2\lambda + \theta}{k'(\lambda + \theta)^2},\quad T_i = 2\lambda + \theta

For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.

Ziegler–Nichols (reaction curve) (P, PI, PID)
Kc=0.9 τKθ,Ti=3.33 θK_c = \frac{0.9\,\tau}{K\theta},\quad T_i = 3.33\,\theta

The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.

Cohen–Coon (P, PI, PID)
Kc=τKθ(0.9+θ12τ),Ti=θ 30+3θ/τ9+20θ/τK_c = \frac{\tau}{K\theta}\Big(0.9 + \frac{\theta}{12\tau}\Big),\quad T_i = \theta\,\frac{30 + 3\theta/\tau}{9 + 20\theta/\tau}

Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.

AMIGO (Åström–Hägglund) (PI, PID)
Kc=0.15K+(0.35−θτ(θ+τ)2)τKθ,Ti=0.35θ+13θτ2τ2+12θτ+7θ2K_c = \frac{0.15}{K} + \Big(0.35 - \frac{\theta\tau}{(\theta+\tau)^2}\Big)\frac{\tau}{K\theta},\quad T_i = 0.35\theta + \frac{13\theta\tau^2}{\tau^2 + 12\theta\tau + 7\theta^2}

Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.

How to implement it

  • Ratio station: SP₂ = R × wild flow, limited to the flow loop's range. Below a minimum wild flow, hold a minimum.
  • Bumpless: in manual, the trim tracks the ratio actually being run, FB/FAF_B/F_A.
  • Windup: while the flow loop is saturated, hold the trim's integral, as in cascade.
  • HMI: show the ratio setpoint and the actual ratio side by side.

Siemens and elsewhere

Siemens
  • No ratio block in PID_Compact: one line of SCL computes the setpoint, as in the exported call, before the flow controller.
  • Use PID_Compact for the flow loop. Use a second one for the trim, its output scaled 0–100 % → [R_min, R_max].
  • Cross-limiting for combustion (air leads fuel up, lags it down) is a MAX/MIN on the two setpoints: the same selector idea as override control.
Elsewhere
  • DCS: RATIO blocks with ratio limits and bias, and a cascade connection to the slave.
  • Combustion control standards (NFPA 85, EN 12952) build on ratio with cross-limiting and an O₂ trim: the same structure as here.

Interactive Controller Sandbox

Test and tune Ratio control live on a process, benchmark against baseline PI, and inspect the resulting code.

Interactive Gains (Outer Loop)

Drag sliders or nudge gains to observe the closed-loop transient response
Kc (gain): 0.5
Ti (integral): 38.6 s
Td (derivative): 0 s

Closed-Loop Response: Ratio vs Baseline PI

Simulating…
Running test scenarios…
Block Diagram
SP rΣ+−PIDTrim PIDR 0–0.5R×diluent (wild) flow (FT-801)SP₂Σ+−Slave PIDFIC-802CV uValve1/(τᵥs + 1)×concentrate supply pressureConcentrate flowm³/hdiluent (wild) flowProcessV·ċ = F_B·c_B − F·cPV yFT-8021/(τₘ₂s + 1)Concentrate flow measuredAT-803e^(−θs)/(τₘs + 1)PV measured
Generated code
// Loop Lab export: In-line blending (ratio), AIC-803
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.

FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
   VAR_INPUT
      Setpoint : Real;        // engineering units
      Input : Real;           // measurement, engineering units
      ManualEnable : Bool;    // TRUE = manual: Output follows ManualValue
      ManualValue : Real;     // %
      Feedforward : Real;     // %, added to the output (0 when unused)
      HoldIntegral : Int;     // +1 / -1: don't integrate up / down (a cascade slave is saturated)
      ExtResetEnable : Bool;  // override: this controller is not selected, so its integral follows ExtReset
      ExtReset : Real;        // %, the selected (valve) output, for external reset feedback
      Cycle : Real := 0.5;    // s, must match the cyclic interrupt the block is called from
   END_VAR
   VAR_OUTPUT
      Output : Real;          // %
      AtLimit : Int;          // +1 / -1 when the output is pinned high / low
   END_VAR
   VAR
      Gain : Real := 0.5;        // % output per % of span
      Ti : Real := 38.6;          // s, 0 = no integral action
      Td : Real := 0.0;          // s, 0 = no derivative action
      PWeighting : Real := 1.0;   // setpoint weight b on P
      DWeighting : Real := 0.0;   // setpoint weight c on D
      TdFiltRatio : Real := 0.1;  // derivative filter = TdFiltRatio * Td
      InLow : Real := 0.0;
      InHigh : Real := 20.0;
      OutLow : Real := 0.0;
      OutHigh : Real := 100.0;
      Invert : Bool := FALSE;
      Integral : Real;        // integral term, in % output (so gain changes don't bump)
      DTerm : Real;
      LastED : Real;
   END_VAR
   VAR_TEMP
      sp : Real;
      pv : Real;
      dir : Real;
      e : Real;
      eP : Real;
      eD : Real;
      p : Real;
      tf : Real;
      iNext : Real;
      v : Real;
      u : Real;
   END_VAR

BEGIN
    // Scale to % of span: the gains are then independent of engineering units.
    #sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
    #pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
    #dir := 1.0;
    IF #Invert THEN
        #dir := -1.0;
    END_IF;
    #e := #dir * (#sp - #pv);
    #eP := #dir * (#PWeighting * #sp - #pv);
    #eD := #dir * (#DWeighting * #sp - #pv);
    #p := #Gain * #eP;

    IF #ManualEnable THEN
        // Track: preload the integral so switching to auto doesn't bump the output.
        #u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
        #Integral := #u - #p - #Feedforward;
        #DTerm := 0.0;
        #LastED := #eD;
        #Output := #u;
        #AtLimit := 0;
        RETURN;
    END_IF;

    // Derivative on c*SP - PV through a first-order filter (backward Euler).
    IF #Td > 0.0 THEN
        #tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
        #DTerm := #tf / (#tf + #Cycle) * #DTerm
                  + #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
    ELSE
        #DTerm := 0.0;
    END_IF;
    #LastED := #eD;

    IF #ExtResetEnable AND #Ti > 0.0 THEN
        // External reset feedback: the integral follows the selected output through a Ti lag,
        // so this controller's output is the valve signal plus its own P and D.
        #iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
    ELSIF #Ti > 0.0 THEN
        #iNext := #Integral + #Gain * #Cycle / #Ti * #e;
    ELSE
        #iNext := #Integral;
    END_IF;

    #v := #p + #iNext + #DTerm + #Feedforward;
    #u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);

    // A saturated slave asks its master to stop integrating in that direction.
    IF #ExtResetEnable THEN
        #Integral := #iNext;
    ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
        // Conditional integration: stop integrating while the output is pinned and the error pushes it further.
        IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
            #Integral := #iNext;
        END_IF;
    END_IF;

    IF #v > #OutHigh THEN
        #AtLimit := 1;
    ELSIF #v < #OutLow THEN
        #AtLimit := -1;
    ELSE
        #AtLimit := 0;
    END_IF;
    #Output := #u;
END_FUNCTION_BLOCK

// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "AT-803" is the scaled input (NORM_X/SCALE_X from the analog card), "FV-802" the output to scale back to 0-27648.
// Ratio station: FIC-802 setpoint = R × FT-801 (diluent (wild) flow).
// Give the flow controller its own tuning once at start-up (OB100): "FIC_802_DB".Gain := 0.88; "FIC_802_DB".Ti := 1.75; "FIC_802_DB".InLow := 0.0; "FIC_802_DB".InHigh := 25.0;
// Trim: AIC-803 sets R over 0.0–0.5; in manual it tracks the ratio being run, so auto is bumpless.
"AIC_803_DB"(Setpoint := "SP", Input := "AT-803", ManualEnable := "Manual", ManualValue := ("FT-802" / MAX(IN1 := "FT-801", IN2 := 0.001) - 0.0) / 0.5 * 100.0, HoldIntegral := "FIC_802_DB".AtLimit);
"Ratio" := 0.0 + "AIC_803_DB".Output / 100.0 * 0.5;
"SP2" := LIMIT(MN := 0.0, IN := "Ratio" * "FT-801", MX := 25.0);
"FIC_802_DB"(Setpoint := "SP2", Input := "FT-802", ManualEnable := "Manual", ManualValue := "ManualOut");
"FV-802" := "FIC_802_DB".Output;