PID with feedforward
Act on a disturbance as soon as it is measured, before it moves the PV. Feedback still runs alongside to clean up what the feedforward gets wrong.
Theory
If a measured disturbance reaches the PV through and the valve through , the output that cancels it exactly is
With first-order-plus-dead-time models of both paths, that becomes a gain, a lead-lag and (sometimes) a delay:
- Static feedforward (the gain alone) gets the steady state right. It is often enough, and it comes straight from a mass or energy balance.
- Lead-lag fixes the timing when the two paths have different speeds.
- If the ideal feedforward would need to see the future. It can only be partly cancelled, and feedback has to do the rest.
Stability. Feedforward is outside the loop, so it doesn't change the stability margins at all. A wrong feedforward makes the response worse, never unstable.
When it works, and when it breaks
Big, frequent disturbances that can be measured upstream: throughput, feed temperature, feed composition.
Processes with dead time, where feedback alone reacts too late.
Where a balance (mass, energy) gives the gain without any test.
Unmeasured disturbances: there is nothing to feed forward.
Disturbances that reach the PV faster than the valve can: only partial cancellation.
Wrong or drifting models: fouling, valve wear, a mis-ranged transmitter. Too much feedforward makes upsets worse.
A failed transmitter: feedforward follows the bad reading straight into the valve.
How to tune it
- Static gain first: from a balance, or from two bump tests (output step → PV, disturbance step → PV) as . Start at 70–80 % of it.
- Lead-lag: lead = , lag = . If they are close, leave both at zero.
- Test with real disturbance steps, with feedback in automatic.
- The PV first dips, then rises: the timing is wrong.
- The PV ends up away from setpoint while feedback catches up: the gain is wrong.
- Re-check after maintenance: feedforward gains drift with the plant.
The tuning rules in the lab
Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.
The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.
Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.
For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.
The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.
Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.
Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.
How to implement it
- Use the deviation from the disturbance value when the loop went to automatic, so switching on is bumpless.
- Add the feedforward to the PID output inside the anti-windup (the integral sees the total output), or to a cascade slave's setpoint.
- Re-zero in manual, limit its contribution, and freeze it on a bad-quality input.
- Discretize the lead-lag with backward Euler at the controller cycle.
Siemens and elsewhere
- PID_Compact: newer versions have a Disturbance input added to the output; check your version.
- Otherwise: compute the feedforward in SCL (the exported LL_LeadLag block) and add it through LL_PID's Feedforward input, or to the cascade slave's setpoint.
- Bad quality: use the analog input's status (or the PROFINET IO status) to freeze the feedforward.
- DCS: most PID blocks have a feedforward input with its own gain, and many have lead-lag blocks for the dynamic part.
- Rockwell: the PIDE instruction has a feedforward input.
- Ratio control is the common special case: a flow kept in proportion to another (fuel to air, additive to main flow) is feedforward with a gain set by the ratio.
Interactive Controller Sandbox
Test and tune PID with feedforward live on a process, benchmark against baseline PI, and inspect the resulting code.
Interactive Gains (Primary Loop)
Drag sliders or nudge gains to observe the closed-loop transient responseClosed-Loop Response: Feedforward vs Baseline PI
Simulating…// Loop Lab export: Steam heat exchanger, TIC-301
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.
FUNCTION_BLOCK "LL_LeadLag"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
In : Real; // the measured disturbance, engineering units
Reset : Bool; // TRUE (e.g. in manual): re-zero on the present value
Gain : Real; // % per unit of the disturbance
Lead : Real; // s
Lag : Real; // s
Delay : Real := 0.0; // s, wait before acting (up to 1000 cycles)
Cycle : Real := 0.5;
END_VAR
VAR_OUTPUT
Out : Real; // %, zero at the value it started from
END_VAR
VAR
Started : Bool;
X0 : Real;
XPrev : Real;
Y : Real;
Past : Array[0..999] of Real; // the lead-lag's output over the last Delay
Head : Int;
END_VAR
VAR_TEMP
x : Real;
n : Int;
i : Int;
END_VAR
BEGIN
// Deviation from where the loop was switched on, so feedforward starts bumpless.
IF #Reset OR NOT #Started THEN
#X0 := #In;
#XPrev := 0.0;
#Y := 0.0;
FOR #i := 0 TO 999 DO
#Past[#i] := 0.0;
END_FOR;
#Head := 0;
#Started := TRUE;
END_IF;
#x := #In - #X0;
// Backward Euler of (Lead*s + 1) / (Lag*s + 1).
#Y := #Lag / (#Lag + #Cycle) * #Y
+ (#Lead + #Cycle) / (#Lag + #Cycle) * #x
- #Lead / (#Lag + #Cycle) * #XPrev;
#XPrev := #x;
// Dead time: the value from Delay ago, out of a ring of the last n cycles.
#n := REAL_TO_INT(#Delay / #Cycle);
IF #n > 1000 THEN
#n := 1000;
END_IF;
IF #n <= 0 THEN
#Out := #Gain * #Y;
ELSE
IF #Head >= #n THEN
#Head := 0;
END_IF;
#Out := #Gain * #Past[#Head];
#Past[#Head] := #Y;
#Head := (#Head + 1) MOD #n;
END_IF;
END_FUNCTION_BLOCK
FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
Setpoint : Real; // engineering units
Input : Real; // measurement, engineering units
ManualEnable : Bool; // TRUE = manual: Output follows ManualValue
ManualValue : Real; // %
Feedforward : Real; // %, added to the output (0 when unused)
HoldIntegral : Int; // +1 / -1: don't integrate up / down (a cascade slave is saturated)
ExtResetEnable : Bool; // override: this controller is not selected, so its integral follows ExtReset
ExtReset : Real; // %, the selected (valve) output, for external reset feedback
Cycle : Real := 0.5; // s, must match the cyclic interrupt the block is called from
END_VAR
VAR_OUTPUT
Output : Real; // %
AtLimit : Int; // +1 / -1 when the output is pinned high / low
END_VAR
VAR
Gain : Real := 1.5; // % output per % of span
Ti : Real := 29.0; // s, 0 = no integral action
Td : Real := 0.0; // s, 0 = no derivative action
PWeighting : Real := 1.0; // setpoint weight b on P
DWeighting : Real := 0.0; // setpoint weight c on D
TdFiltRatio : Real := 0.1; // derivative filter = TdFiltRatio * Td
InLow : Real := 0.0;
InHigh : Real := 120.0;
OutLow : Real := 0.0;
OutHigh : Real := 100.0;
Invert : Bool := FALSE;
Integral : Real; // integral term, in % output (so gain changes don't bump)
DTerm : Real;
LastED : Real;
END_VAR
VAR_TEMP
sp : Real;
pv : Real;
dir : Real;
e : Real;
eP : Real;
eD : Real;
p : Real;
tf : Real;
iNext : Real;
v : Real;
u : Real;
END_VAR
BEGIN
// Scale to % of span: the gains are then independent of engineering units.
#sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
#pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
#dir := 1.0;
IF #Invert THEN
#dir := -1.0;
END_IF;
#e := #dir * (#sp - #pv);
#eP := #dir * (#PWeighting * #sp - #pv);
#eD := #dir * (#DWeighting * #sp - #pv);
#p := #Gain * #eP;
IF #ManualEnable THEN
// Track: preload the integral so switching to auto doesn't bump the output.
#u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
#Integral := #u - #p - #Feedforward;
#DTerm := 0.0;
#LastED := #eD;
#Output := #u;
#AtLimit := 0;
RETURN;
END_IF;
// Derivative on c*SP - PV through a first-order filter (backward Euler).
IF #Td > 0.0 THEN
#tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
#DTerm := #tf / (#tf + #Cycle) * #DTerm
+ #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
ELSE
#DTerm := 0.0;
END_IF;
#LastED := #eD;
IF #ExtResetEnable AND #Ti > 0.0 THEN
// External reset feedback: the integral follows the selected output through a Ti lag,
// so this controller's output is the valve signal plus its own P and D.
#iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
ELSIF #Ti > 0.0 THEN
#iNext := #Integral + #Gain * #Cycle / #Ti * #e;
ELSE
#iNext := #Integral;
END_IF;
#v := #p + #iNext + #DTerm + #Feedforward;
#u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);
// A saturated slave asks its master to stop integrating in that direction.
IF #ExtResetEnable THEN
#Integral := #iNext;
ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
// Conditional integration: stop integrating while the output is pinned and the error pushes it further.
IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
#Integral := #iNext;
END_IF;
END_IF;
IF #v > #OutHigh THEN
#AtLimit := 1;
ELSIF #v < #OutLow THEN
#AtLimit := -1;
ELSE
#AtLimit := 0;
END_IF;
#Output := #u;
END_FUNCTION_BLOCK
// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "TT-301" is the scaled input (NORM_X/SCALE_X from the analog card), "FV-301" the output to scale back to 0-27648.
"FF_F_DB"(In := "FT-302", Reset := "Manual", Gain := 5.0, Lead := 0.0, Lag := 0.0);
"FF_Tin_DB"(In := "TT-302", Reset := "Manual", Gain := -1.24, Lead := 0.0, Lag := 0.0);
"TIC_301_DB"(Setpoint := "SP", Input := "TT-301", ManualEnable := "Manual", ManualValue := "ManualOut", Feedforward := "FF_F_DB".Out + "FF_Tin_DB".Out);
"FV-301" := "TIC_301_DB".Output;