The flow loop: when PI is the answer
Can anything beat a well-tuned PI on a fast, noisy flow loop, and what would it cost?
The situation
A header supplies water through FV-101 and a magflow FT-101. Operators move the setpoint between about 15 and 45 m³/h, and other users on the header pull its pressure around. The physics is in the mechanical view: an equal-percentage valve with low authority installs nearly linear, and the water's inertia is negligible. The loop's dynamics are the actuator (1.5 s) and the transmitter (0.5 s).
Start crude: on-off
The cheapest controller there is. Watch the valve column: it swings between shut and wide open, the flow cycles around the setpoint, and the valve travels hundreds of strokes an hour. That is fine for a sump pump, and not for a control valve.
A PI by the Lambda method
The bump test (or the control view's linearization) gives , s and s. Lambda tuning with cancels the valve lag, and s gives . The result is clean first-order responses, header upsets rejected within seconds, and moderate valve travel.
Push harder: SIMC with τc = θ
The "as fast as robustly possible" setting quadruples the gain. IAE improves, but look at the cost: the noise on the reading now reaches the valve (CV activity about 4×, valve travel about 2.5×), and the setpoint steps overshoot by up to a third. Small dead time means you can tune fast, but noise and wear mean you usually shouldn't.
Add derivative?
Derivative adds phase lead, but this process has very little lag to recover. Its filter-limited high-frequency gain multiplies the measurement noise: the scorecard improves by a few percent at best while valve travel more than doubles. On a flow loop D is almost always off.
When the valve is the problem
A 1 % deadband and 2 % noise. With integral action, the controller slowly winds the output across the deadband, the valve jumps, the flow overshoots, and the cycle repeats: a stick-slip limit cycle. Lower gains only slow it down. The fix is mechanical (positioner, packing), which is why the commissioning checklist strokes the valve before tuning.
Verdict
PI, Lambda- or SIMC-tuned with a moderate gain.
- Nothing on the controller ladder buys enough to justify its complexity here.
- Effort is better spent on the valve: sizing, deadband, positioner.
- Keep the gain where the valve isn't chasing noise.