Liquid flow loop
Water from a pressure header through a control valve and a magnetic flowmeter. Fast, noisy and self-regulating: the classic loop where a well-tuned PI is all you need.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeDead time θ0.3 snothing happens for this long after the valve moves
Time constant τ1.75 sthen 63 % of the way in this long
Gain K1.61% of span the PV moves per % of valve
Lag-dominant (θ/τ < 0.2) — Easy for PIDelay share: 14.6% (θ/τ = 0.17)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 30 m³/h:
Verdict: PID is the answer
PI, and leave it there. A Lambda- or SIMC-tuned PI with a moderate gain controls this loop well over the whole range and through header upsets. Derivative improves the scorecard by a few percent at best, and more than doubles the valve travel. On-off cycles the valve hundreds of times an hour. If the loop misbehaves, look at the valve (deadband, sizing) before the controller.