Exothermic batch reactor
A batch reaction that gives off heat, faster the hotter it gets. At the start of the batch that positive feedback eats most of the jacket’s cooling margin: the reactor is four times slower and more sensitive than at the end, and a stronger batch can outrun the jacket altogether. One fixed tuning sees different plants.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeA PI struggles through a whole batch. Derivative or state feedback hold it, as long as the recipe leaves cooling to spare.
- A PI commissioned on a quiet batch (Kc 0.88) has Ms 2.6 when a full charge is in, and a strong batch overshoots by 2.4 °C; at the worst corner of the ±20 % spread, by up to 24 °C.
- Tuned for the start of the batch (SIMC, Kc 0.47) it is robust there (Ms 1.3) but lags the 2 °C/min heat-up by 26 °C. Slow the ramp or add the ramp's feedforward.
- The self-tuning PI, starting from the quiet-batch tuning, learns its way to Ms 1.4 at the start of the batch and no overshoot. But its estimate wanders when nothing moves: late in a quiet hold it detuned itself to Kc 0.25.
- ADRC holds the start of the batch with Ms 1.6 and no model beyond b₀, but lags ramps.
- PID, tuned hard on the tests (Kc 10.6, Td 84 s), follows the ramps and stays within about 3 °C at every corner of the spread: its derivative pays for the gain. It has no margin left at 95 °C, above where these batches run.
- State feedback does the same with about 40 % less error and stays stable everywhere in the spread (Ms 2.4 at 80 °C, 4.5 at 95 °C). It needs a model of the reactor and jacket.
No controller can cool harder than the jacket can. A fast enough loop can hold a reactor that would run away on its own, but it then depends entirely on that loop and on cooling to spare. Once the reaction makes more heat than full cooling removes, the temperature goes, whatever the loop does. That is fixed in the recipe (dosing, slower heat-up, a cleaner jacket) and guarded by the safety system, not in the loop.