In-line blending (ratio)

A concentrate dosed into a diluent stream that the plant upstream sets. Production changes the diluent flow all the time; the concentration should not care. The textbook case for ratio control.

Plant Dynamics at Nominal Point

FOPDT dynamics & controllability regime
Open on the bench🧩 Build in Block Studio
Dead time θ24.3 snothing happens for this long after the valve moves
Time constant τ38.5 sthen 63 % of the way in this long
Gain K1% of span the PV moves per % of valve
Balanced (0.2 ≤ θ/τ < 1) — ModerateDelay share: 38.6% (θ/τ = 0.63)
0% Pure lag (fast PI)50% Balanced100% Pure delay (needs Smith / MPC)
Linearized model at 10 %:
G(s)≈1 e−24.3s38.5s+1G(s) \approx \frac{1\,e^{-24.3s}}{38.5s + 1}
Verdict: PID falls short

Ratio control with an analyzer trim.

  • Production changes drop from 27 % of span (5 %-points) on the product to under 1 %.
  • The trim handles the concentrate's strength.
  • The trim's loop gain no longer depends on the rate. Additive feedforward handles the throughput nearly as well, but its trim overshoots 28–32 % at low rate where the ratio trim overshoots 10–13 %. On the mismatch test, ratio's IAE is a third of feedforward's.

A fixed ratio without a trim is fine only if the concentrate never varies.