Cascade control
Two loops nested: a fast inner (slave) loop on a variable between the valve and the PV, and an outer (master) loop that sets the slave's setpoint. Upsets that pass through the inner variable are corrected before they reach the PV.
Theory
The master controls the main PV. Its output is the slave's setpoint, and the slave controls a faster intermediate variable, here steam flow, by moving the valve.
What it buys.
- Inner upsets are fixed early. Anything that disturbs the inner variable (supply pressure, a valve that sticks) is corrected by the slave before it reaches the main PV.
- The master sees a simpler process. With the slave closed, the valve's nonlinearity, stiction and supply variations disappear inside it. The master sees "steam flow → temperature", which is cleaner than "valve position → temperature".
What it needs.
- The slave must be clearly faster than the master: a crossover 3–5× higher at least. Otherwise the two loops fight.
- The inner variable must be measurable, and reached by the valve before the outer variable.
In the frequency domain. The master sees , the slave's closed loop, in series with the path to the PV. At frequencies well below the slave's bandwidth that is close to 1: the master doesn't see the inner dynamics.
When it works, and when it breaks
An upset enters through a fast, measurable intermediate variable: supply pressure → flow, a jacket temperature, a motor current.
The valve or actuator is nonlinear or sticky: an inner flow or position loop straightens it out.
Temperature, level and composition loops whose valves have positioners or flow meters.
The inner loop is not much faster than the outer: they interact, and the result is worse than one loop.
Upsets that bypass the inner variable (process flow, inlet temperature here): cascade does nothing for them.
Windup through the cascade: if the master keeps integrating while the slave is saturated, the recovery overshoots.
Mode handling: a slave left in manual or local setpoint silently breaks the loop.
How to tune it
- Slave first, on its own, with a local setpoint: fast and well damped (SIMC with is usually fine for a flow loop).
- Close the slave. Bump-test the master by stepping the slave's setpoint, and fit a model to that response.
- Tune the master on that model, more slowly: its crossover well below the slave's.
- Check both loops' margins: the analysis here shows them separately.
The tuning rules in the lab
Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.
The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.
Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.
For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.
The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.
Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.
Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.
How to implement it
- Scale the master's output (0–100 %) to the slave's setpoint range.
- Run the slave after the master in the same cycle, or in a faster cyclic interrupt.
- Manual mode: the master tracks the slave's measurement, so switching to automatic is bumpless.
- Windup: stop the master integrating in a direction where the slave is saturated (external reset feedback does this more elegantly).
- Feedforward for a cascade usually goes into the slave's setpoint.
Siemens and elsewhere
- PID_Temp supports cascade directly: master and slave configured to work together, including what happens when the slave can't follow.
- PID_Compact: two instances. Master Output → scaled → slave Setpoint, and handle the master's windup when the slave is at a limit. The exported LL_PID has HoldIntegral and AtLimit for this.
- HMI: show both loops on the faceplate, with the slave's mode visible.
- DCS PID blocks have a cascade mode (often called CAS). The slave sends its actual setpoint back (back-calculation) so the master can initialise and avoid windup.
- Motion control is cascade throughout: current inside velocity inside position, each loop several times faster than the one outside it.
Interactive Controller Sandbox
Test and tune Cascade control live on a process, benchmark against baseline PI, and inspect the resulting code.
Interactive Gains (Outer Loop)
Drag sliders or nudge gains to observe the closed-loop transient responseClosed-Loop Response: Cascade vs Baseline PI
Simulating…// Loop Lab export: Steam heat exchanger, TIC-301
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.
FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
Setpoint : Real; // engineering units
Input : Real; // measurement, engineering units
ManualEnable : Bool; // TRUE = manual: Output follows ManualValue
ManualValue : Real; // %
Feedforward : Real; // %, added to the output (0 when unused)
HoldIntegral : Int; // +1 / -1: don't integrate up / down (a cascade slave is saturated)
ExtResetEnable : Bool; // override: this controller is not selected, so its integral follows ExtReset
ExtReset : Real; // %, the selected (valve) output, for external reset feedback
Cycle : Real := 0.5; // s, must match the cyclic interrupt the block is called from
END_VAR
VAR_OUTPUT
Output : Real; // %
AtLimit : Int; // +1 / -1 when the output is pinned high / low
END_VAR
VAR
Gain : Real := 1.5; // % output per % of span
Ti : Real := 31.0; // s, 0 = no integral action
Td : Real := 0.0; // s, 0 = no derivative action
PWeighting : Real := 1.0; // setpoint weight b on P
DWeighting : Real := 0.0; // setpoint weight c on D
TdFiltRatio : Real := 0.1; // derivative filter = TdFiltRatio * Td
InLow : Real := 0.0;
InHigh : Real := 120.0;
OutLow : Real := 0.0;
OutHigh : Real := 100.0;
Invert : Bool := FALSE;
Integral : Real; // integral term, in % output (so gain changes don't bump)
DTerm : Real;
LastED : Real;
END_VAR
VAR_TEMP
sp : Real;
pv : Real;
dir : Real;
e : Real;
eP : Real;
eD : Real;
p : Real;
tf : Real;
iNext : Real;
v : Real;
u : Real;
END_VAR
BEGIN
// Scale to % of span: the gains are then independent of engineering units.
#sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
#pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
#dir := 1.0;
IF #Invert THEN
#dir := -1.0;
END_IF;
#e := #dir * (#sp - #pv);
#eP := #dir * (#PWeighting * #sp - #pv);
#eD := #dir * (#DWeighting * #sp - #pv);
#p := #Gain * #eP;
IF #ManualEnable THEN
// Track: preload the integral so switching to auto doesn't bump the output.
#u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
#Integral := #u - #p - #Feedforward;
#DTerm := 0.0;
#LastED := #eD;
#Output := #u;
#AtLimit := 0;
RETURN;
END_IF;
// Derivative on c*SP - PV through a first-order filter (backward Euler).
IF #Td > 0.0 THEN
#tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
#DTerm := #tf / (#tf + #Cycle) * #DTerm
+ #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
ELSE
#DTerm := 0.0;
END_IF;
#LastED := #eD;
IF #ExtResetEnable AND #Ti > 0.0 THEN
// External reset feedback: the integral follows the selected output through a Ti lag,
// so this controller's output is the valve signal plus its own P and D.
#iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
ELSIF #Ti > 0.0 THEN
#iNext := #Integral + #Gain * #Cycle / #Ti * #e;
ELSE
#iNext := #Integral;
END_IF;
#v := #p + #iNext + #DTerm + #Feedforward;
#u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);
// A saturated slave asks its master to stop integrating in that direction.
IF #ExtResetEnable THEN
#Integral := #iNext;
ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
// Conditional integration: stop integrating while the output is pinned and the error pushes it further.
IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
#Integral := #iNext;
END_IF;
END_IF;
IF #v > #OutHigh THEN
#AtLimit := 1;
ELSIF #v < #OutLow THEN
#AtLimit := -1;
ELSE
#AtLimit := 0;
END_IF;
#Output := #u;
END_FUNCTION_BLOCK
// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "TT-301" is the scaled input (NORM_X/SCALE_X from the analog card), "FV-301" the output to scale back to 0-27648.
// Cascade: TIC-301 (master) sets the steam flow setpoint; FIC-301 (slave) drives the valve.
// Give the slave its own tuning once at start-up (OB100): "FIC_301_DB".Gain := 1.8; "FIC_301_DB".Ti := 2.25; "FIC_301_DB".Td := 0.0; "FIC_301_DB".InLow := 0.0; "FIC_301_DB".InHigh := 2000.0;
// In manual the master tracks the slave's measurement, so switching to auto is bumpless.
"TIC_301_DB"(Setpoint := "SP", Input := "TT-301", ManualEnable := "Manual", ManualValue := ("FT-301" - 0.0) / 2000.0 * 100.0, Feedforward := 0.0, HoldIntegral := "FIC_301_DB".AtLimit);
"SP2" := 0.0 + "TIC_301_DB".Output / 100.0 * 2000.0;
"FIC_301_DB"(Setpoint := "SP2", Input := "FT-301", ManualEnable := "Manual", ManualValue := "ManualOut");
"FV-301" := "FIC_301_DB".Output;