Characterized PID

Undo a known nonlinearity before the PID sees it, so that the controller faces a linear process. It works on the measurement (control volume instead of level) or on the output (the inverse valve characteristic).

Theory

If the process is a known static nonlinearity in series with something linear, invert the nonlinearity.

  • On the measurement: control y′=f(y)y' = f(y) instead of yy, with the setpoint converted the same way. In the conical tank, V(h)V(h) turns A(h) h˙=Qin−QoutA(h)\,\dot h = Q_{in} - Q_{out} into V˙=Qin−Qout\dot V = Q_{in} - Q_{out}, whose gain doesn't depend on level.
  • On the output: send s=g−1(v)s = g^{-1}(v) to the actuator. The controller asks for a flow fraction vv and gets it whatever the valve's inherent curve.

The PID then sees an approximately linear process and one tuning applies everywhere. Unlike scheduling, it adds no dynamics of its own and no extra loop through the gains.

When it works, and when it breaks

Works
  • Nonlinearities that are static and known: vessel geometry, valve characteristics, the square root of a DP flowmeter, a titration curve.

  • When the nonlinear function is well defined, but bump tests at many points are impractical.

Breaks
  • Nonlinearities that are dynamic or unknown.

  • Wrong models: the inversion is only as good as the formula (see the mismatch test).

  • Near flat spots (f′o0f' o 0) the inverse has huge gain and amplifies noise.

  • Output characterization inverts the inherent curve, not the installed one, so line losses remain.

How to tune it

  1. Put the characterization in first, then bump-test in the characterized units: the gain should now be the same at every operating point.
  2. Tune one PI with your usual rule.
  3. Test at the extremes of the range, and with the model deliberately off by 10–20 %.
The tuning rules in the lab
SIMC (Skogestad) (PI, PID)
Kc=τK(τc+θ),Ti=min⁡(τ, 4(τc+θ))K_c = \frac{\tau}{K(\tau_c + \theta)},\quad T_i = \min\big(\tau,\ 4(\tau_c + \theta)\big)

Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.

Lambda (IMC) (PI)
Kc=τK(λ+θ),Ti=τK_c = \frac{\tau}{K(\lambda + \theta)},\quad T_i = \tau

The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.

IMC-PID (Rivera–Morari–Skogestad) (PI, PID)
Kc=2τ+θ2Kλ,Ti=τ+θ2PID: Kc=2τ+θK(2λ+θ), Td=τθ2τ+θK_c = \frac{2\tau + \theta}{2K\lambda},\quad T_i = \tau + \frac{\theta}{2}\qquad\text{PID: } K_c = \frac{2\tau + \theta}{K(2\lambda + \theta)},\ T_d = \frac{\tau\theta}{2\tau + \theta}

Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.

Lambda for integrating (averaging level) (P, PI)
Kc=2λ+θk′(λ+θ)2,Ti=2λ+θK_c = \frac{2\lambda + \theta}{k'(\lambda + \theta)^2},\quad T_i = 2\lambda + \theta

For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.

Ziegler–Nichols (reaction curve) (P, PI, PID)
Kc=0.9 τKθ,Ti=3.33 θK_c = \frac{0.9\,\tau}{K\theta},\quad T_i = 3.33\,\theta

The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.

Cohen–Coon (P, PI, PID)
Kc=τKθ(0.9+θ12τ),Ti=θ 30+3θ/τ9+20θ/τK_c = \frac{\tau}{K\theta}\Big(0.9 + \frac{\theta}{12\tau}\Big),\quad T_i = \theta\,\frac{30 + 3\theta/\tau}{9 + 20\theta/\tau}

Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.

AMIGO (Åström–Hägglund) (PI, PID)
Kc=0.15K+(0.35−θτ(θ+τ)2)τKθ,Ti=0.35θ+13θτ2τ2+12θτ+7θ2K_c = \frac{0.15}{K} + \Big(0.35 - \frac{\theta\tau}{(\theta+\tau)^2}\Big)\frac{\tau}{K\theta},\quad T_i = 0.35\theta + \frac{13\theta\tau^2}{\tau^2 + 12\theta\tau + 7\theta^2}

Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.

How to implement it

  • Write the function as a small FC with clamped inputs.
  • Apply the same function to the setpoint as to the measurement.
  • Display both raw and characterized values on the HMI, so operators and engineers each see their own units.
  • Alarms belong on the raw measurement.

Siemens and elsewhere

Siemens
  • Volume from level: an FC (exported as LL_TankVolume) computes it, and PID_Compact's Input and Setpoint are the volumes.
  • Valve linearization: an FC between the PID output and the analog output.
  • Strapping tables: TIA has no built-in table block, so use an FC with an interpolation table, or SCALE_X segments.
Elsewhere
  • DCS: most have "characterizer" function blocks (piecewise-linear tables) for exactly this.
  • Valves: smart positioners often have selectable characterization curves, which do the same thing in the field device.

Interactive Controller Sandbox

Test and tune Characterized PID live on a process, benchmark against baseline PI, and inspect the resulting code.

Interactive Gains (Primary Loop)

Drag sliders or nudge gains to observe the closed-loop transient response
Kc (gain): 3
Ti (integral): 245 s
Td (derivative): 0 s

Closed-Loop Response: Characterization vs Baseline PI

Simulating…
Running test scenarios…
Block Diagram
SP rf(·)SP → vol.Σ+−PIDKc·(1 + 1/Ti·s + Td·s)PIDCV uValve1/(τᵥs + 1), char.stemΣ++d: outlet valve openingProcessA(h)·ḣ = Qᵢₙ − QₒᵤₜPV yTransmittere^(−θs)/(τₘs + 1)Σ++noise nf(·)level → vol.PV measured
Generated code
// Loop Lab export: Conical tank level, LIC-201
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.

FUNCTION "LL_TankVolume" : Real
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
   VAR_INPUT
      Level : Real;       // m
   END_VAR
   VAR CONSTANT
      H_ : Real := 2.0;    // tank height, m
      R_ : Real := 1.0;    // top radius, m
      R0_ : Real := 0.15;  // bottom radius, m
   END_VAR
   VAR_TEMP
      h : Real;
      alpha : Real;
   END_VAR

BEGIN
    // Volume of a cone frustum filled to Level: pi * ((r0 + alpha*h)^3 - r0^3) / (3*alpha).
    #h := LIMIT(MN := 0.0, IN := #Level, MX := #H_);
    #alpha := (#R_ - #R0_) / #H_;
    IF ABS(#alpha) < 1.0E-9 THEN
        #LL_TankVolume := 3.14159265 * #R0_ * #R0_ * #h;
    ELSE
        #LL_TankVolume := 3.14159265 * ((#R0_ + #alpha * #h) ** 3 - #R0_ ** 3) / (3.0 * #alpha);
    END_IF;
END_FUNCTION

FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
   VAR_INPUT
      Setpoint : Real;        // engineering units
      Input : Real;           // measurement, engineering units
      ManualEnable : Bool;    // TRUE = manual: Output follows ManualValue
      ManualValue : Real;     // %
      Feedforward : Real;     // %, added to the output (0 when unused)
      HoldIntegral : Int;     // +1 / -1: don't integrate up / down (a cascade slave is saturated)
      ExtResetEnable : Bool;  // override: this controller is not selected, so its integral follows ExtReset
      ExtReset : Real;        // %, the selected (valve) output, for external reset feedback
      Cycle : Real := 0.5;    // s, must match the cyclic interrupt the block is called from
   END_VAR
   VAR_OUTPUT
      Output : Real;          // %
      AtLimit : Int;          // +1 / -1 when the output is pinned high / low
   END_VAR
   VAR
      Gain : Real := 3.0;        // % output per % of span
      Ti : Real := 245.0;          // s, 0 = no integral action
      Td : Real := 0.0;          // s, 0 = no derivative action
      PWeighting : Real := 1.0;   // setpoint weight b on P
      DWeighting : Real := 0.0;   // setpoint weight c on D
      TdFiltRatio : Real := 0.1;  // derivative filter = TdFiltRatio * Td
      InLow : Real := 0.0;
      InHigh : Real := 2.4557;
      OutLow : Real := 0.0;
      OutHigh : Real := 100.0;
      Invert : Bool := FALSE;
      Integral : Real;        // integral term, in % output (so gain changes don't bump)
      DTerm : Real;
      LastED : Real;
   END_VAR
   VAR_TEMP
      sp : Real;
      pv : Real;
      dir : Real;
      e : Real;
      eP : Real;
      eD : Real;
      p : Real;
      tf : Real;
      iNext : Real;
      v : Real;
      u : Real;
   END_VAR

BEGIN
    // Scale to % of span: the gains are then independent of engineering units.
    #sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
    #pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
    #dir := 1.0;
    IF #Invert THEN
        #dir := -1.0;
    END_IF;
    #e := #dir * (#sp - #pv);
    #eP := #dir * (#PWeighting * #sp - #pv);
    #eD := #dir * (#DWeighting * #sp - #pv);
    #p := #Gain * #eP;

    IF #ManualEnable THEN
        // Track: preload the integral so switching to auto doesn't bump the output.
        #u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
        #Integral := #u - #p - #Feedforward;
        #DTerm := 0.0;
        #LastED := #eD;
        #Output := #u;
        #AtLimit := 0;
        RETURN;
    END_IF;

    // Derivative on c*SP - PV through a first-order filter (backward Euler).
    IF #Td > 0.0 THEN
        #tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
        #DTerm := #tf / (#tf + #Cycle) * #DTerm
                  + #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
    ELSE
        #DTerm := 0.0;
    END_IF;
    #LastED := #eD;

    IF #ExtResetEnable AND #Ti > 0.0 THEN
        // External reset feedback: the integral follows the selected output through a Ti lag,
        // so this controller's output is the valve signal plus its own P and D.
        #iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
    ELSIF #Ti > 0.0 THEN
        #iNext := #Integral + #Gain * #Cycle / #Ti * #e;
    ELSE
        #iNext := #Integral;
    END_IF;

    #v := #p + #iNext + #DTerm + #Feedforward;
    #u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);

    // A saturated slave asks its master to stop integrating in that direction.
    IF #ExtResetEnable THEN
        #Integral := #iNext;
    ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
        // Conditional integration: stop integrating while the output is pinned and the error pushes it further.
        IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
            #Integral := #iNext;
        END_IF;
    END_IF;

    IF #v > #OutHigh THEN
        #AtLimit := 1;
    ELSIF #v < #OutLow THEN
        #AtLimit := -1;
    ELSE
        #AtLimit := 0;
    END_IF;
    #Output := #u;
END_FUNCTION_BLOCK

// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "LT-201" is the scaled input (NORM_X/SCALE_X from the analog card), "LV-201" the output to scale back to 0-27648.
// Control volume rather than level: convert both measurement and setpoint.
"PV_Volume" := "LL_TankVolume"(Level := "LT-201");
"SP_Volume" := "LL_TankVolume"(Level := "SP");
"LIC_201_DB"(Setpoint := "SP_Volume", Input := "PV_Volume", ManualEnable := "Manual", ManualValue := "ManualOut");
"LV-201" := "LIC_201_DB".Output;