Characterized PID
Undo a known nonlinearity before the PID sees it, so that the controller faces a linear process. It works on the measurement (control volume instead of level) or on the output (the inverse valve characteristic).
Theory
If the process is a known static nonlinearity in series with something linear, invert the nonlinearity.
- On the measurement: control instead of , with the setpoint converted the same way. In the conical tank, turns into , whose gain doesn't depend on level.
- On the output: send to the actuator. The controller asks for a flow fraction and gets it whatever the valve's inherent curve.
The PID then sees an approximately linear process and one tuning applies everywhere. Unlike scheduling, it adds no dynamics of its own and no extra loop through the gains.
When it works, and when it breaks
Nonlinearities that are static and known: vessel geometry, valve characteristics, the square root of a DP flowmeter, a titration curve.
When the nonlinear function is well defined, but bump tests at many points are impractical.
Nonlinearities that are dynamic or unknown.
Wrong models: the inversion is only as good as the formula (see the mismatch test).
Near flat spots () the inverse has huge gain and amplifies noise.
Output characterization inverts the inherent curve, not the installed one, so line losses remain.
How to tune it
- Put the characterization in first, then bump-test in the characterized units: the gain should now be the same at every operating point.
- Tune one PI with your usual rule.
- Test at the extremes of the range, and with the model deliberately off by 10–20 %.
The tuning rules in the lab
Model-based, one tuning knob: the closed-loop time constant τc. τc = θ gives a fast, still robust loop (Ms ≈ 1.6); larger τc is smoother. The min() on Ti keeps lag-dominant and integrating processes from responding too slowly to load upsets. PID uses the second-order model: Td = τ2 in series form.
The process-industry favourite: choose λ, the closed-loop time constant, and the setpoint response is first-order with no overshoot. Ti = τ cancels the process pole, which makes load rejection slow on lag-dominant processes. λ = 1–3 × τ is typical for robustness.
Internal model control worked back into a PID (Rivera, Morari and Skogestad, 1986): the controller that makes the loop a first-order λ response, with the dead time replaced by its first-order Padé approximation. That approximation is what gives the derivative, and why Ti = τ + θ/2 rather than τ. Keep λ above about 0.8θ for the PID and 1.7θ for the PI, where the approximation stops holding. Like Lambda, it cancels the process lag, so load upsets on lag-dominant processes recover slowly. The IMC structure itself (the model running beside the plant) is the Smith predictor on the bench.
For integrating processes such as levels, from the ramp rate k′ (% of span per second, per % of output). λ is the arrest time: how long the level keeps moving after an inflow upset. For a step upset Δ (in % of output) the level swings about k′·Δ·λ/e before it turns round, so choose λ from the room the tank has. A long λ lets the tank absorb the upset and keeps the outflow smooth: averaging level control. P-only: Kc = 1/(k′λ), which leaves an offset that is harmless in a buffer.
The 1942 rules, aiming for a quarter-amplitude decay. Aggressive: Ms is often above 2, so the loop rings and is sensitive to model error. Worth knowing because so many loops in the field were tuned this way.
Like Ziegler–Nichols but corrected for dead time, so it copes better when θ/τ is large. Also aimed at quarter-amplitude decay, so also aggressive.
Derived by optimizing load rejection with a robustness limit (Ms ≈ 1.4) over a large test batch of processes. A safe modern default when you have no reason to choose a speed.
How to implement it
- Write the function as a small FC with clamped inputs.
- Apply the same function to the setpoint as to the measurement.
- Display both raw and characterized values on the HMI, so operators and engineers each see their own units.
- Alarms belong on the raw measurement.
Siemens and elsewhere
- Volume from level: an FC (exported as LL_TankVolume) computes it, and PID_Compact's Input and Setpoint are the volumes.
- Valve linearization: an FC between the PID output and the analog output.
- Strapping tables: TIA has no built-in table block, so use an FC with an interpolation table, or SCALE_X segments.
- DCS: most have "characterizer" function blocks (piecewise-linear tables) for exactly this.
- Valves: smart positioners often have selectable characterization curves, which do the same thing in the field device.
Interactive Controller Sandbox
Test and tune Characterized PID live on a process, benchmark against baseline PI, and inspect the resulting code.
Interactive Gains (Primary Loop)
Drag sliders or nudge gains to observe the closed-loop transient responseClosed-Loop Response: Characterization vs Baseline PI
Simulating…// Loop Lab export: Conical tank level, LIC-201
// TIA Portal SCL (S7-1200 / S7-1500). Generated code: review before use on a real plant.
FUNCTION "LL_TankVolume" : Real
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
Level : Real; // m
END_VAR
VAR CONSTANT
H_ : Real := 2.0; // tank height, m
R_ : Real := 1.0; // top radius, m
R0_ : Real := 0.15; // bottom radius, m
END_VAR
VAR_TEMP
h : Real;
alpha : Real;
END_VAR
BEGIN
// Volume of a cone frustum filled to Level: pi * ((r0 + alpha*h)^3 - r0^3) / (3*alpha).
#h := LIMIT(MN := 0.0, IN := #Level, MX := #H_);
#alpha := (#R_ - #R0_) / #H_;
IF ABS(#alpha) < 1.0E-9 THEN
#LL_TankVolume := 3.14159265 * #R0_ * #R0_ * #h;
ELSE
#LL_TankVolume := 3.14159265 * ((#R0_ + #alpha * #h) ** 3 - #R0_ ** 3) / (3.0 * #alpha);
END_IF;
END_FUNCTION
FUNCTION_BLOCK "LL_PID"
{ S7_Optimized_Access := 'TRUE' }
VERSION : 0.1
VAR_INPUT
Setpoint : Real; // engineering units
Input : Real; // measurement, engineering units
ManualEnable : Bool; // TRUE = manual: Output follows ManualValue
ManualValue : Real; // %
Feedforward : Real; // %, added to the output (0 when unused)
HoldIntegral : Int; // +1 / -1: don't integrate up / down (a cascade slave is saturated)
ExtResetEnable : Bool; // override: this controller is not selected, so its integral follows ExtReset
ExtReset : Real; // %, the selected (valve) output, for external reset feedback
Cycle : Real := 0.5; // s, must match the cyclic interrupt the block is called from
END_VAR
VAR_OUTPUT
Output : Real; // %
AtLimit : Int; // +1 / -1 when the output is pinned high / low
END_VAR
VAR
Gain : Real := 3.0; // % output per % of span
Ti : Real := 245.0; // s, 0 = no integral action
Td : Real := 0.0; // s, 0 = no derivative action
PWeighting : Real := 1.0; // setpoint weight b on P
DWeighting : Real := 0.0; // setpoint weight c on D
TdFiltRatio : Real := 0.1; // derivative filter = TdFiltRatio * Td
InLow : Real := 0.0;
InHigh : Real := 2.4557;
OutLow : Real := 0.0;
OutHigh : Real := 100.0;
Invert : Bool := FALSE;
Integral : Real; // integral term, in % output (so gain changes don't bump)
DTerm : Real;
LastED : Real;
END_VAR
VAR_TEMP
sp : Real;
pv : Real;
dir : Real;
e : Real;
eP : Real;
eD : Real;
p : Real;
tf : Real;
iNext : Real;
v : Real;
u : Real;
END_VAR
BEGIN
// Scale to % of span: the gains are then independent of engineering units.
#sp := (#Setpoint - #InLow) / (#InHigh - #InLow) * 100.0;
#pv := (#Input - #InLow) / (#InHigh - #InLow) * 100.0;
#dir := 1.0;
IF #Invert THEN
#dir := -1.0;
END_IF;
#e := #dir * (#sp - #pv);
#eP := #dir * (#PWeighting * #sp - #pv);
#eD := #dir * (#DWeighting * #sp - #pv);
#p := #Gain * #eP;
IF #ManualEnable THEN
// Track: preload the integral so switching to auto doesn't bump the output.
#u := LIMIT(MN := #OutLow, IN := #ManualValue, MX := #OutHigh);
#Integral := #u - #p - #Feedforward;
#DTerm := 0.0;
#LastED := #eD;
#Output := #u;
#AtLimit := 0;
RETURN;
END_IF;
// Derivative on c*SP - PV through a first-order filter (backward Euler).
IF #Td > 0.0 THEN
#tf := MAX(IN1 := #TdFiltRatio * #Td, IN2 := 1.0E-6);
#DTerm := #tf / (#tf + #Cycle) * #DTerm
+ #Gain * #Td / (#tf + #Cycle) * (#eD - #LastED);
ELSE
#DTerm := 0.0;
END_IF;
#LastED := #eD;
IF #ExtResetEnable AND #Ti > 0.0 THEN
// External reset feedback: the integral follows the selected output through a Ti lag,
// so this controller's output is the valve signal plus its own P and D.
#iNext := #Integral + #Cycle / MAX(IN1 := #Ti, IN2 := #Cycle) * (#ExtReset - #Integral);
ELSIF #Ti > 0.0 THEN
#iNext := #Integral + #Gain * #Cycle / #Ti * #e;
ELSE
#iNext := #Integral;
END_IF;
#v := #p + #iNext + #DTerm + #Feedforward;
#u := LIMIT(MN := #OutLow, IN := #v, MX := #OutHigh);
// A saturated slave asks its master to stop integrating in that direction.
IF #ExtResetEnable THEN
#Integral := #iNext;
ELSIF #Ti > 0.0 AND NOT ((#HoldIntegral > 0 AND #iNext > #Integral) OR (#HoldIntegral < 0 AND #iNext < #Integral)) THEN
// Conditional integration: stop integrating while the output is pinned and the error pushes it further.
IF NOT ((#v > #OutHigh AND #iNext > #Integral) OR (#v < #OutLow AND #iNext < #Integral)) THEN
#Integral := #iNext;
END_IF;
END_IF;
IF #v > #OutHigh THEN
#AtLimit := 1;
ELSIF #v < #OutLow THEN
#AtLimit := -1;
ELSE
#AtLimit := 0;
END_IF;
#Output := #u;
END_FUNCTION_BLOCK
// OB30 "Cyclic interrupt", cycle time 0.5 s (500 ms).
// "LT-201" is the scaled input (NORM_X/SCALE_X from the analog card), "LV-201" the output to scale back to 0-27648.
// Control volume rather than level: convert both measurement and setpoint.
"PV_Volume" := "LL_TankVolume"(Level := "LT-201");
"SP_Volume" := "LL_TankVolume"(Level := "SP");
"LIC_201_DB"(Setpoint := "SP_Volume", Input := "PV_Volume", ManualEnable := "Manual", ManualValue := "ManualOut");
"LV-201" := "LIC_201_DB".Output;