Conical tank level
A point-down conical tank. The cross-section grows several times from bottom to top, so the process gain and speed change across the range: one PI tuning cannot be right everywhere.
Plant Dynamics at Nominal Point
FOPDT dynamics & controllability regimeCharacterize if you know the geometry; gain-schedule if you don't; or accept one PI tuned for the top. Controlling volume gives one PI tuning that is right from bottom to top, costs a single function block, and survives moderate geometry errors. Gain scheduling reaches the same result from bump tests at a few levels, without needing a formula, at the cost of more parameters to look after. What both buy is margin more than error: they hold Ms at about 1.5 at every level. A single PI tuned fast enough for the top comes within about 10 % on error, but runs at Ms 1.8 near the bottom, with seven times the gain it needs there. The PI to avoid is the one tuned at the bottom: sluggish, then ringing, higher up.