The reactor: split-range heating and cooling
One temperature controller, a steam valve and a cooling water valve. Why does a loop that was fine during start-up start hunting once the reaction is running?
The situation
R-501 needs steam to get warm and cooling water once the reaction runs. TIC-501's output is split: 0–50 % opens the cooling water (fully open at 0), 50–100 % opens the steam.
The mechanical view plots the heat into the jacket against the controller output. The line is three and a half times steeper on the cooling side: per % of output, cooling water moves far more heat than steam.
Tuned during start-up, on steam
The loop was commissioned while heating up the first batch, so it was tuned on the steam side: SIMC with , , s. On steam it is fine.
Once the reaction needs cooling, the loop gain is 3.5 times higher, and the linear analysis says the loop is unstable on that side. In the simulation it doesn't run away: every swing back across the split puts it on the low-gain side again. Instead it hunts, bouncing the output between cooling water and steam. Valve travel is 14 strokes an hour, three times a well-behaved loop's, with steam and cooling water fighting each other.
Detune for the cooling side
The usual fix on site: lower the gain until the cooling side is calm. Tuned on the cooling side (, s), the loop is stable everywhere with Ms 2.3.
The steam side is now sluggish. Setpoint steps that need steam overshoot by about 23 % and take 10–12 minutes to settle.
Balance the split
Give the cooling valve more of the range: split at about 76 %, the ratio of the two capacities, . Now each % of output moves about 10 kW on either side. One SIMC tuning (, s) fits both.
Result.
- Setpoint steps overshoot 5–8 % on both sides, settling in 5–9 minutes.
- Load swings are rejected with 40 % less IAE than the detuned loop.
- Ms is the same 2.4 everywhere.
The characterized controller does the same thing in software: it maps the controller's output onto the two valves at the balance point, so the valves' split can stay at 50 %. The two give identical results.
The gap
A gap between the ranges (both valves shut over a band) stops steam and cooling water ever being on together. It is also a dead zone.
With a 6 % gap, a reactor running near the split wanders four times more (IAE 8 instead of 2): the controller has to integrate across the gap before either valve moves. Valve activity doubles as it hops across.
The characterization can jump the gap in software, but then a tiny change in output moves a valve by a step. Keep the gap as small as the valves' shut-off allows.
Verdict
Balance the split, then tune one loop.
- Put the split point where both ranges move the same heat per % (or characterize the output in the PLC), keep the gap small, and tune once.
- If the cooling capacity changes a lot with the seasons, re-check the balance in summer and winter.
The ladder's rung here is characterization, not anything fancier: the problem is a nonlinearity in the actuators, so straighten it. After that, derivative is worth having if the valves can take it: it halves the load swings for about seven times the travel.