The compressor: a limit you must never cross

One recycle valve holds the discharge pressure and keeps the compressor out of surge. What does it take to do both, when a user can trip at any moment?

🌀 Compressor near surgePID falls short7 guided steps
Step 1
Step 1 of 7

The situation

A fixed-speed compressor feeds a header at 6 bar. The users take about 45 kNm³/h; the recycle valve UV-1101 spills back the rest of the 55 the machine delivers at that pressure. The mechanical view has the curve: the higher the pressure, the less flow, and past 6.6 bar none at all. There the machine surges, with the flow reversing and the bearings taking a beating every few seconds. The surge approach (surge flow over actual flow) is 54 % at 6 bar. At 100 % the machine is on its surge line.

Step 2
Step 2 of 7

Baseline: a pressure PI

A PI on the discharge pressure (Kc=1.1K_c = 1.1, Ti=4.3T_i = 4.3 s, more valve → less pressure, so it acts in reverse). Setpoint changes and ordinary demand changes are fine. Then the biggest user trips: 40 kNm³/h less taken in an instant. The pressure climbs 0.7 bar a second, and on the flat top of the curve the flow falls away. 1.4 s after the trip the machine is past its surge line (the approach reaches 204 %), and it surges again before the pressure loop has caught up.

Running the tests…
Step 3
Step 3 of 7

Tune the pressure loop harder?

Four times the gain and half the integral time keep this trip out of surge (the approach peaks at 70 %), but the loop is now far too lively for the users: a 0.9 bar setpoint step down undershoots to 5.1 bar. And it does nothing for the other way to surge. When demand is low and someone asks for more pressure than the machine can make, the PI closes the recycle and walks the machine onto its surge line at any speed.

Comparing in this step:Pressure PIPressure PI, tuned hard
Running the tests…
Step 4
Step 4 of 7

An anti-surge override

Add a second controller, UIC-1101, on the surge approach, with its setpoint on a control line at 80 % and fast tuning (Kc=8K_c = 8, Ti=1T_i = 1 s). Normally it is pinned shut and the pressure PI has the valve; a high selector hands the valve to whichever wants it more open. With the setpoint ramped up to 6.8 bar, the pressure PI closes the recycle, the approach reaches the control line, and the override takes over: the approach peaks at 87 % and the pressure settles at 6.59 bar, where the machine is safe, short of what was asked.

The trip still surges (190 %). The approach only rises once the flow has fallen, on the flat top of the curve, which leaves a fraction of a second. A wider margin only buys a little: the measurement is always late.

Comparing in this step:Pressure PIAnti-surge override
Running the tests…
Step 5
Step 5 of 7

Feedforward from the users' flow

FT-1102 measures the users' flow, so the trip is known the moment it happens. Every kNm³/h the users stop taking has to go round the recycle: 0.75 % of valve per kNm³/h at 6 bar. Design from model finds the same gain, with a lead and lag that nearly cancel. Added to the pressure PI's output, it opens the valve as the trip happens. The pressure barely moves (6.2 bar at most) and the approach peaks at 58 %. But a setpoint past the curve still surges: feedforward knows about the users, not about the curve.

Comparing in this step:Pressure PIPressure PI + feedforward
Running the tests…
Step 6
Step 6 of 7

Both together

The override with the feedforward on the pressure controller's output: the trip is caught as it happens, and the control line holds against anything slower. No surge in any test: the approach peaks at 58 % on the trip and at 87 % with the setpoint pushed too high.

Comparing in this step:Anti-surge overrideOverride + feedforward
Running the tests…
Verdict
Step 7 of 7

Verdict

An ordinary pressure PI, an anti-surge controller on a control line through a high selector, and feedforward for the upsets you can measure.

  • The pressure loop is tuned for the users. Tuning it to protect the machine makes it worse at its job and still misses half the cases.
  • The override guards the limit against anything slow enough for a measurement to catch.
  • Feedforward handles the trip, which no feedback on this machine is fast enough for.
  • Real anti-surge systems add a recycle trip line (a step open past the control line), faster opening than closing, and a fast valve. The principle is the one here: act before the flow falls.

Everything in this case, through every test